PSFC Diborane Emergency
PSFC Diborane Emergency
Plasma Science and Fusion Center
Office of Environment, Safety, and Health
190 Albany Street, NW21 2nd floor
617-253-8440 (Catherine Fiore)
617-253-8917 (Matt Fulton)
617-253-5982 (Bill Byford)
617-258-5473 (Nancy Masley)
Fax 617-252-1808
Be Safe or Die
Reviewed and Approved By:
PSFC Supervisor--Earl Marmar
PSFC Supervisor--Jim Irby
PSFC Safety Officer--Catherine L. Fiore
Emergency Procedures for Diborane Gas System
PSFC-CH-95004
Authors: Catherine L. Fiore, Chris Reddy, Joe Bosco
Version: 3.3
Date: 1/16/96, Updated 5/30/03 by C. Fiore
Persons Responsible: Gary Dekow - NW21-106
Catherine Fiore - NW21-203
Jim Irby- NW21-186
Introduction
The Alcator C-Mod experiment will operate discharge cleaning on several
occasions using a mixture of diborane (10%) and helium. Diborane is
highly toxic and flammable. This document postulates several emergency
situations, and details what is to be done if they arise.
Scope/Purpose
This document covers the emergency procedures
for the Alcator C-Mod Diborane facility.
Consequences of procedural failure
Failure to properly react in the event of emergency could
result in the unnecessary exposure of personal to harmful levels of
diborane gas.
Diborane is immediately dangerous to life and health at 40 ppm, and
an explosion hazard at 9000 ppm.
Definitions
MDA-TLD-1 Gas monitor for the diborane system.
One is located at the diborane gas cabinet. The other is located
close to the igloo mounted on the diagnostic stand near the diborane
cabinet.
SCBASelf Contained Breathing Apparatus. Two units are located
at the entrance to the C-Mod power room, in the control room. Two more units
are currently being purchased. Until these are on site, two units should
be borrowed from the MIT Industrial Hygiene Office in building 56 and kept
on site during a boronization process.
Responsibilities
Emergency response will be the responsibility of two of the following
people:
- Catherine Fiore,
- Andy Pfeiffer,
- Jim Irby,
- Gary Dekow,
- Bill Cochran,
with the backup by members of the MIT
Industrial Hygiene Office and the Cambridge Fire Department if necessary.
Should an entry into the cell wearing SCBA be made, 4 SCBA qualified people
must be present.
These procedures will be reviewed and approved by a committee of
no less than 3 knowledgeable persons, appointed by the Safety Officer.
Required Equipment
- SCBA
- Wrenches for gas fittings
- Walkie-talkies or cell phones
Required Materials
Assumptions and Prerequisites
It is assumed that the diborane monitors are installed in the
cell and are functioning, as detailed in the diborane system test procedure.
It is assumed that an alarm on the diborane monitors triggers
a loud bell and annunciator, and that all personnel will evacuate the
cell and power room in response to this alarm.
If any element of the diborane safety system is not operational, the
diborane is to be removed from the cell. (Refer to Procedure for Installation/Deinstallation of Diborane Gas.)
Procedure
Note: The diborane alarm signal latches once it is triggered, and must be reset at the detector in order to stop the alarm. Ocasional problems with the meters have triggered faults at times when a diborane leak was extremely unlikely to have occurred. In the event that an alarm is sounded at a time when the bottle is locked in the cabinet and it has not been opened, it is most likely safe to check and reset the meter if the following conditions are true:
- Both monitor readings at the Diborane PLC read 0ppb and their history registers 0ppb.
- The cabinet pressure is negative
- No problem can be seen on the visual tv monitor at the cabinet (channel 27).
If these conditions are verified, then a pair of workers should proceed to the cell, maintaining verbal contact with workers in the control room to check for and correct a meter fault.
If the diborane bottle has been opened or there is any sign that the bottle or gas cabinet has been breached, use the following emergency procedures.
- SCBA personnel in trouble.
SCBA users always work in pairs. It is most likely that if one SCBA
person gets into trouble, the other will be able to summon help via the
radio, the cell phone, or by exiting the cell to ask for assistance. If at
any point an emergency occurs, EMT's should be summoned by dialing 100 before
taking any other steps.
In any event, the rescuers must make reasoned judgements about the extent
of risk they are willing to take in the case that assistance is needed.
Any rescuer needs to ascertain the cause and circumstances surrounding
the emergency in order to avoid adding more victims or aggravating injuries.
Sound and reasoned judgement must be brought to bear in a case such as this.
If the diborane bottle valve is closed, and the exhaust system is functioning,
and the diborane monitors are reading 0, then it may be best to proceed with
rescue without SCBA gear, especially if it appears that time is critical.
(The exhaust system can be checked by looking at TR8 on the CRYBOR screen.
It should be reading greater than 0.25")
Several possible scenarios could result in the necessity of rescuing
one of the SCBA wearing personnel, not all related to the toxic gas system.
These include accidental injury by fall or impact, heart attack or other
spontaneous medical event, failure of the SCBA, inhalation of toxic gas, or
explosion of the toxic gas system.
The first step of the rescuers should be to summon the EMT's. The standby
personnel should then don the SCBA and come to the aid of the persons in the
cell. One of them should take all possible steps to secure the gas system,
i.e., shut the manual valve on the gas bottle if it can be reached safely. If
they judge it safe to do so, they could try to remove the victim to a safe
location if the cell cannot be rendered safe to proceed with treatment.
Should the people in the control room lose contact with both SCBA entrants,
then the EMT's should be summoned immediately. The backup team can then don
the SCBA and carefully enter the cell to try and find the problem.
An extra diborane meter is located in Catherine Fiore's office and can be used
to check the atmosphere if necessary. This should be done
very cautiously in order to avoid having additional victims.
- Diborane leak detected in gas box or cell, cell closed.
- Set the TV to channel 27 to monitor the gas cabinet.
- Check the status of the diborane system on the PLC. The
automatic valve (PV5) above the diborane bottle should have closed at the alarm
initiation.
- If this valve has closed, monitor the output of the diborane
detector. It updates once every minute. If the level does not decrease after
several minutes, institute a Purge5.
- If the level still does not decrease after several minutes, summon two
people from the emergency contact list. Notify the Industrial Hygiene Office
that backup is needed. Call 3-2596 (the Industrial Hygiene Office) between the
hours of 9 to 5. Outside of regular working hours,
call the facilities operations center(3-1500) and ask them to
notify the on call Industrial Hygienist, specifying that two additional SCBA
units may be needed, if they are not already four sets in the control room.
If at any point, it appears that a fire is in progress, dial 100 to activate a
full emergency response. (Set the tv camera to channel 27 to monitor the
cabinet.) If no fire is indicated, proceed to the next step.
- Two qualified persons should don the SCBA apparatus and prepare to
enter the cell. Once two additional SCBA qualified persons have arrived and
two additional SCBA units are on site, the first crew may enter the cell. They
must maintain radio or cell phone contact with the backup SCBA crew. (Those wearing
SCBA need to hold the walkie-talkie under the air outlet on the mask to make
themselves audible.) They should proceed to close the valve at the diborane
bottle. They should check the diborane monitor which is exhibiting an alarm
and verify visually that it is reading at an alarm level. If it is reading 0 at
the meter, then the tape can be inspected visually for brown dots which
indicate that a diborane leak did actually occur. They should then exit the
cell.
- If a leak is confirmed on the tape, a PURGE 60 should be done once
the bottle valve is closed and the SCBA crew has exited.
- The cell evacuation should remain in effect until the diborane
monitor indicates that the diborane level has fallen to a safe level. Once
it has, the cell can be entered to reset the toxic gas monitor and to
assess the reason for the fault.
- If a leak is confirmed, and PURGE60 does not clear it, dial 100 and
tell them that there is an uncontrolled toxic/flammable gas leak. Make sure
they summon the on-call Industrial Hygienest as well as the fire department.
- Diborane leak detected in gas box or cell, cell open.
All personnel must evacuate the cell. If the cell has not
been closed, then it is assumed that there is no diborane in the process
lines, and that any leak must be in the region of the gas bottle. Therefore,
no attempt to purge the gas lines needs to be made.
- If this valve has closed, monitor the output of the diborane
detector. It updates once every minute. If the level does not decrease after
several minutes, summon two people from the emergency contact list. Notify the
Industrial Hygiene Office that backup is needed. Call 3-2596 or ask the
physical plant operations to notify the on call Industrial Hygienist,
specifying that two additional SCBA units may be needed, if they are not
already there. At any point, if it appears that a fire is in progress, dial
100 and activate a full emergency response. (Set the tv camera to channel 27 to
monitor the cabinet.)
- Two qualified persons should don the SCBA apparatus and prepare to
enter the cell. Once two additional SCBA qualified persons have arrived and
two additional SCBA units are on site, the first crew may enter the cell. They
must maintain radio or cell phone contact with the backup SCBA crew. (Those
wearing SCBA need to hold the walkie-talkie under the air outlet on the mask
to make themselves audible.) If the cell is open, the manual valve on the
diborane bottle should not be open or have been opened. They should first
attempt to reset the meter which is in alarm. Then they should verify that
the valve at the diborane bottle is closed. They should check that the gas
cabinet has not been damaged in some manner to start a gas leak. If the meter
can be reset and is reading 0, then the tape should be inspected visually for
brown dots which indicate that a diborane leak did actually occur. If it is
clear, the cell can be returned to normal access.
- If the meter appears to be malfunctioning, then the spare MDA-TLD1
should be obtained from Catherine Fiore's office. It should be supplied with
a fresh tape and used to verify that the cell and gas cabinet are free from
diborane gas. It can then be swapped with the malfunctioning instrument,
which can be removed for diagnosis and repair. If no spare meter is available
and it is certain that the problem is due to meter malfunction, then the
diborane bottle should be removed from the cell until the meter can be returned
to service. (Refer to Procedure for
Installation/Deinstallation of Diborane Gas.)
- The cell evacuation should remain in effect until the diborane
monitor indicates that the diborane level has fallen to a safe level. Once
it has, the cell can be entered to reset the toxic gas monitor and to
assess the reason for the fault.
- Fire in cell
- Evacuate the cell and building and summon emergency response
personnel by dialing 100. Inform them that an MIT Industrial
Hygienist will be needed in addition to the normal notification list and
the fire department.
- A command center will be set up outside the building by the
emergency response team. Go to the person in charge and inform him
of the presence of toxic, flammable diborane gas in the cell, and tell them
where it is located.
- No PSFC personnel should take further action unless directed to do so
by the person directing the emergency response on behalf of MIT Facilities or
Cambridge Fire Department.
- Damage to the diborane gas cabinet
- If diborane gas is detected, and it is expected that an
extensive release is occurring, evacuate the building by pulling
one of the fire pull boxes. Dial 100 and initiate emergency response
just as in the case of a fire, requesting the presence of an Industrial
Hygienist in addition to the normal notification list and the fire
department. Continue the procedure for having a fire in the cell.
- If no diborane gas is detected, and there is no reason to
suspect a malfunction of the diborane gas monitor, then two of the designated
emergency personnel will prepare
to don SCBA in order to assess the situation. They should proceed with
step 3.
- Notify the Industrial Hygiene Office
that backup is needed. Call 3-2596 or ask the physical plant operations
to notify the on call Industrial Hygienist, specifying that
two additional SCBA units are needed if two extra units are not already
at the site. At any point, if it appears
that a fire is in progress, dial 100 to activate a full emergency response
as in section IV.
- Two qualified persons from the emergency response list should don the
SCBA apparatus and prepare to enter the cell. Once two SCBA qualified persons
have arrived and two additional SCBA units are on site, the first crew may
enter the cell. They must maintain radio or cell phone contact with the backup
SCBA crew. They should examine the status of the cabinet and gas bottle, and
proceed to close the valve on the diborane bottle. If the integrity of the gas
cabinet is compromised, they should remove the gas bottle and block it (replace
the plug, which is stored with the diborane bottle), and remove it to the
exterior gas storage shed. (Refer to Procedure for
Installation/Deinstallation of Diborane Gas.) If it is to be removed, they should ask the
contact person in the control room to see that unnecessary personnel leave the
area along the transport route, i.e. the control room and main hall of NW21.
Note: Catherine Fiore has the key to the gas cabinet and to the toxic gas shed
in her key box. If necessary, the gas bottle can be placed in the vacuum shop
hood temporarily until that key can be obtained. Bill Byford and Rejean Boivin
know how to access the key box in Catherine's Office.
- Power outage during boronization
Maintain the periphery in a locked and secured status. Remain in the
control room until power is restored. If diborane is in the vacuum vessel,
contact Bob Childs or Tom Toland and get them to come in to ensure that
Torvac is properly restarted once power has been restored. Notify Gary Dekow or Catherine Fiore and
get them to come in if they are not already there. Evacuate the machine and
initiate the diborane shutdown
procedure once it is safe to do so.
Do not enter the cell without SCBA under any circumstances!
Checklist
- If a fire in progress then
- Pull the nearest fire alarm.
- Dial 100.
- Inform the emergency personnel that a fire is in progress and that toxic
flammable gas could be involved.
- Request that the on call Industrial Hygeniest be summoned.
- Await the fire department outside the building and inform them of the
situation.
- If the gas cabinet been damaged then
- If diborane gas leak has been detected then
- Pull the nearest fire alarm.
- Dial 100.
- Inform the emergency personnel a toxic flammable gas is in uncontrolled
release, and that a fire could erupt spontaneously.
- Request that the on call Industrial Hygeniest be summoned.
- Await the fire department outside the building and inform them of the
situation.
- Otherwise, proceed with removal of the diborane gas bottle. (Refer to Procedure for Installation/Deinstallation of Diborane Gas.)
- If a diborane gas leak been detected and the cell is locked out then
- Summon backup SCBA qualified personnel.
- Ensure that a total of 4 SCBA units are on hand.
- Verify that PV5 has closed.
- Initiate a Purge5.
- If the diborane level returns to zero then
- Once 4 SCBA qualified personnel and 4 SCBA units are on
hand, two people should don the SCBA units.
- The SCBA persons should enter the cell and shut the diborane gas botttle
valve.
- The SCBA persons should reset the diborane monitor.
- The SCBA persons should exit the cell.
- A purge 60 should be initiated to remove the remainder of the gas from
the system.
- The cell should be reentered, and the diborane tapes checked for brown
spots.
- If the tapes indicate that there was no actual diborane leak, then the
process can be resumed under the assumption that it was a false alarm.
- If a the tapes indicate a true release, then the system must be repaired
and leak checked before proceeding.
- If the diborane level does not return to zero then
- Summon a person knowledgeable in the PLC ladder logic for the diborane
system.
- Once 4 SCBA qualified personnel and 4 SCBA units are on hand, two
people should don the SCBA units.
- The SCBA persons should enter the cell and shut the diborane gas botttle
valve.
- The SCBA persons should exit the cell.
- A purge 60 should be initiated to remove the remainder of the gas from
the system. This will require overriding the interlock in the PLC ladder
logic which prevents PV5 from opening while the diborane monitor is in alarm.
- If the the diborane meter has returned to zero then proceed with
deinstallation of the diborane gas bottle. (Refer to Procedure for
Installation/Deinstallation of Diborane Gas.)
- Otherwise
- Pull the nearest fire alarm.
- Dial 100.
- Inform the emergency personnel a toxic flammable gas is in uncontrolled
release, and that a fire could erupt spontaneously.
- Request that the on call Industrial Hygeniest be summoned.
- Await the fire department outside the building and inform them of the
situation.
- If diborane gas leak has been detected and the cell is not locked out
for boronization then
- Evacuate the cell
- Assemble 4 SCBA qualified people.
- If the diborane reading on the Crybor PLC has returned to zero then
- Have two SCBA qualified persons don SCBA and enter the cell.
- They should reset the meter.
- They should check the diborane meter tape.
- If there is no evidence of diborane (brown circles) on the tape, they
can exit and re-open the cell.
- If there is evidence of diborane, they should return to the control room
and proceed to deinstall the diborane gas bottle. (Refer to Procedure for
Installation/Deinstallation of Diborane Gas.)
- Otherwise
- The backup diborane monitor should be obtained and set up
with a fresh diborane tape.
- Two SCBA qualified persons should don SCBA and enter the cell, with the
backup diborane monitor operating. If this unit goes into alarm they should
exit immediately and proceed to step 4.
- They should check the diborane monitor tape on the alarming unit and verify
that diborane gas is present, by checking for brown spots on the tape.
- If the presence of diborane gas is confirmed, then
- Pull the nearest fire alarm.
- Dial 100.
- Inform the emergency personnel a toxic flammable gas is in uncontrolled
release, and that a fire could erupt spontaneously.
- Request that the on call Industrial Hygeniest be summoned.
- Await the fire department outside the building and inform them of the
situation.
- If there is no evidence of diborane on the tape, and the meter cannot
be reset, then they should replace it with the backup unit.
- If this does not work, then the diborane gas bottle should be deinstalled
until the problem is resolved.
- If building power is lost:
- Remain in the control room until the power is restored.
- Contact Gary Dekow or Catherine Fiore and get one of then to come in.
- If the vacuum vessel has been filled with diborane gas, call Bob
Childs or Tom Toland and get one of them to come in.
- If necessary, have Bob or Tom restart Torvac and evacuate the vacuum
vessel. If cell entry is required for restart, it must be done by two
SCBA qualified persons using the SCBA.
- Proceed with the diborane shutdown procedure.
Training
Those responsible should review these procedures in detail, and
should receive training in toxic gas hazards, and SCBA usage (including
use of walkie-talkie or cell phone units with SCBA.)
Cross references
Distribution
E. Marmar, J. Irby, C. Reddy, R. Clifford, J. Bosco, B. Childs, I.
Hutchinson, F. Silva
References
- Matheson gas catalogue.
- MDA Scientific `` TLD-1 Toxic Gas Detector Operating Instructions''
- Diborane MSDS
This page maintained by Catherine L.
Fiore FIORE@PSFC.MIT.EDU