FIRST POWER TURN-ON
UTILITY CONSOLE IN CONTROL ROOM
SELECT THE PUMPS SCREEN
SELECT COOLDOWN MODE
VERIFY AT LEAST TWO PUMPS
TURN ON
VERIFY THE PRESSURE IS GREATER
THAN 60 PSI
125VDC SWITCH
TURN ON
SWITCH
13.8KV POWER DISTRIBUTION CENTER
CHECK TO SEE IF CB 1 THROUGH
5 ARE OUT OF LOCK STOP
(KEYS SHOULD BE IN 2 O'CLOCK POSITION)
CHECK FAULT INDICTORS ON
CB 1 THROUGH 5
OH2 COMMUTATION SWITCH
TURN ON CB1 AND CB2
START HEAT EXCHANGER FAN
PUSH RESET BUTTON
EF1 COMMUTATION SWITCH
TURN ON CB1 AND CB2
START HEAT EXCHANGER FAN
PUSH RESET BUTTON
COMMUTATION POWER PANEL
TURN ON CB10 CHOPPER CONTROL
CHOPPER POWER SUPPLY
PUSH RESET BUTTON ON IOC
BOARD.
RED LED SHOULD LIGHT
POWER PANEL NO.1
TURN ON CB 20 TF CONTROL
POWER
TURN ON CB 23 TMX CONTROL
POWER
OH-EF POWER PANEL
TURN ON CB 1 THROUGH 14
TURN ON CB 15, 17 AND 19
EF4 CABINETS
TURN ON MAIN POWER
TO CONTROL CABINET USING DISCONNECT SWITCH
TURN ON UPS POWER
TO FORWARD CONVERTOR CABINET
TURN ON 120 VAC POWER TO
FORWARD CONVERTOR CABINET
TURN ON UPS POWER
TO REVERSE CONVERTOR CABINET
TURN ON 120 VAC POWER TO
REVERSE CONVERTOR CABINET
TOGGLE SWITCH 03/13 "RESET"
IN PLC RACK
TF AUX.CONTROL CABINET 1
TURN ON UPS CONTROL POWER
(TOGGLE SWITCH)
START HEAT EXCHANGER FAN
PUSH RESET BUTTON
TF AUX.CONTROL CABINET 2
TURN ON UPS CONTROL POWER
(TOGGLE SWITCH)
START HEAT EXCHANGER FAN
PUSH RESET BUTTON
TF AUX.CONTROL CABINET 3
TURN ON UPS CONTROL POWER
(TOGGLE SWITCH)
START HEAT EXCHANGER FAN
PUSH RESET BUTTON
TF AUX.CONTROL CABINET 4
TURN ON UPS CONTROL
POWER (TOGGLE SWITCH)
START HEAT EXCHANGER FAN
PUSH RESET BUTTON
TF BYPASS CONTROL CABINET
TURN ON UPS CONTROL POWER
(TOGGLE SWITCH)
START HEAT EXCHANGER FAN
PUSH RESET BUTTON
OH2U AUX. CONTROL CABINET
TURN ON UPS CONTROL POWER
(TOGGLE SWITCH)
START HEAT EXCHANGER FAN
PUSH RESET BUTTON
OH2L AUX.CONTROL CABINET
TURN ON UPS CONTROL
POWER (TOGGLE SWITCH)
START HEAT EXCHANGER FAN
PUSH RESET BUTTON
OH1 CROWBAR CABINET
TURN ON UPS CONTROL POWER
(TOGGLE SWITCH)
OH1 AUX. CONTROL CABINET
START HEAT EXCHANGER
FAN
PUSH RESET BUTTON
EF3 PLC SLIM MODULE
TOGGLE SWITCH 01/11 AUX
POWER ON
TOGGLE SWITCH 03/13 RESET
EF3 POWER SUPPLY
RESET BREAKERS ON KU401C
MODULES
CHECK CONRROL SWITCH IS
IN REMOTE POSITION
CHECK AUXILIARY SWITCH IS
IN AUX ON POSTITION
CHECK BACKUP TIMER IS SET
TO 4.OO SEC
EF1 AUX. CONTROL CABINET
TURN ON CONTROL XFMR
POWER CB
START HEAT EXCHANGER FAN
PUSH RESET BUTTON
CHOPPER CONTROL PANEL
TURN ON POWER
TOGGLE SWITCH 00/10 RESET
LOCATED ON TMX PLC RACK SIM MODULE
VERIFY EFC CONTROL STATUS
OF CHOPPER CONTROL LEDS
(THE FOLLOWING LEDS SHOULD BE ON:
MOD1 DUMP COM. (2ND FROM TOP)
MOD4 DUMP COMM (1ST FROM TOP)
MOD4 INVERT P.S.(2ND FROM TOP)
MOD4 READY (3RD FROM TOP))
EF1 COMMUTATION SWITCH CONTROL CABINET
TURN ON CB1 AND CB2
EF1 MASTER CONTROL CABINET
TURN ON CONTROL POWER
CHECK DUTY CYCLE AND PULSE
DURATION TIMERS (003M & 035(0.1S))
CHECK LOCAL/REMOTE SWITCH
IS SET TO REMOTE
EF1 PLC RACK
TOGGLE SWITCH 03/13 RESET
OH1 COMMUTATION SWITCH
TURN ON CB1 AND CB2
OH1 MASTER CONTROL CABINET
TURN ON CONTROL POWER
CHECK DUTY CYCLE AND PULSE
DURATION TIMERS (003M & 035(0.1S))
CHECK LOCAL/REMOTE SWITCH
IS SET TO REMOTE
OH1 PLC RACK
TOGGLE SWITCH 03/13 RESET
TF MASTER CONTROL CABINET
TURN ON CONTROL POWER
CHECK DUTY CYCLE AND PULSE
DURATION TIMERS (003M & 060(0.1S))
CHECK LOCAL/REMOTE SWITCH
IS SET TO REMOTE
TF PLC RACK
TOGGLE SWITCH 03/13 RESET
OH2U MASTER CONTROL CABINET
TURN ON CONTROL POWER
CHECK DUTY CYCLE AND PULSE
DURATION TIMERS (003M & 035(0.1S))
CHECK LOCAL/REMOTE SWITCH
IS SET TO REMOTE
OH2 COMMUTATION SWITCH
TURN ON CB1 AND CB2
OH2L MASTER CONTROL CABINET
TURN ON CONTROL POWER
CHECK DUTY CYCLE AND PULSE
DURATION TIMERS (003M & 035(0.1S))
CHECK LOCAL/REMOTE SWITCH
IS SET TO REMOTE
OH2 PLC RACK
TOGGLE SWITCH 03/13 RESET
UPS POWER SUPPLY
CHECK MESSAGES ON LCD SCREEN
NOTE AN ERRORS
NOTE LOAD PERCENTAGE
OH1 COMMUTATION SWITCH
PUSH RESET BUTTON
FINALLY CHECK
MAKE ANOTHER PASS THROUGH THE
POWER ROOM
AND VERIFY ALL THE CABINET LIGHTS
ARE ON.
SECOND POWER TURN-ON
OH1 SPELLMAN POWER SUPPLIES
TURN ON POWER
TURN ON HIGH VOLTAGE
OH2 SPELLMAN POWER SUPPLIES
TURN ON POWER
TURN ON HIGH VOLTAGE
EF1 SPELLMAN POWER SUPPLIES
TURN ON POWER
TURN ON HIGH VOLTAGE
PRIOR TO
COMPLETING THE NEXT TWO STEPS
DON THE ARC PROTECTION CLOTHING LOCATED
IN THE LOCKER NEXT TO THE TF CABINET. THE
ARC PROCTECTION EQUIPMENT THAT MUST BE
WORN INCLUDES A COAT, HARD HAT, SAFETY GLASSES,
FACE SHIELD AND GLOVES.
*********************************************************
480V POWER DISTRIBUTION CENTER
CLOSE CBT 11 EF2U A, B
CLOSE CBT 12 EF2L A, B
CLOSE CBT 13 EF2L C, D
CLOSE CBT 21 EFC A, B, C
CLOSE CBT 22 EF2U C, D
CLOSE
CBT 24 CORRECTION COIL CABINETS
TMX POWER SUPPLIES
PUSH RESET BUTTON
CLOSE CIRCUIT BREAKER
PUSH RESET BUTTON
*********************************************************