FILE: PRE_RUN_POWER_ROOM_TURN_ON_PROCEDURE.HTML
AUTHER: Gary L. Dekow
VERSION: Version 3
DATE: 8/08/2002; Last Update 03/23/06

SAFETY GLASSES AND HARD HATS ARE MANDATORY
EQUIPMENT FOR COMPLETING THE POWER TURN-ON
PROCEDURE.

FIRST POWER TURN-ON

UTILITY CONSOLE IN CONTROL ROOM
        SELECT THE PUMPS SCREEN
        SELECT COOLDOWN MODE
        VERIFY AT LEAST TWO PUMPS TURN ON
        VERIFY THE PRESSURE IS GREATER THAN 60 PSI

UPS POWER SUPPLY
        CHECK MESSAGES ON LCD SCREEN
        NOTE ANY ERRORS
        NOTE LOAD PERCENTAGE

125VDC SWITCH
        TURN ON SWITCH      

13.8KV POWER DISTRIBUTION CENTER
        CHECK TO SEE IF CB 1 THROUGH 5 ARE OUT OF LOCK STOP
            (KEYS SHOULD BE IN 2 O'CLOCK POSITION)
        CHECK FAULT INDICTORS ON CB 1 THROUGH 5

OH1 COMMUTATION SWITCH
        TURN ON CB1 AND CB2
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

OH2 COMMUTATION SWITCH
        TURN ON CB1 AND CB2
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

EF1 COMMUTATION SWITCH
        TURN ON CB1 AND CB2
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

COMMUTATION POWER PANEL
        TURN ON CB10 CHOPPER CONTROL

CHOPPER POWER SUPPLY
        PUSH RESET BUTTON ON IOC BOARD.
        RED LED SHOULD LIGHT

POWER PANEL NO.1
        TURN ON CB 20 TF CONTROL POWER
        TURN ON CB 23 TMX CONTROL POWER

OH-EF POWER PANEL
        TURN ON CB 1 THROUGH 14
        TURN ON CB 15, 17 AND 19

EF4 CABINETS
      TURN ON MAIN POWER TO CONTROL CABINET USING DISCONNECT SWITCH
      TURN ON UPS POWER TO FORWARD CONVERTOR CABINET
        TURN ON 120 VAC POWER TO FORWARD CONVERTOR CABINET
       TURN ON UPS POWER TO REVERSE CONVERTOR CABINET
        TURN ON 120 VAC POWER TO REVERSE CONVERTOR CABINET
        TOGGLE SWITCH 03/13 "RESET" IN PLC RACK

TF AUX.CONTROL CABINET 1
      TURN ON UPS CONTROL POWER (TOGGLE SWITCH)
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

TF AUX.CONTROL CABINET 2
      TURN ON UPS CONTROL POWER (TOGGLE SWITCH)
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

TF AUX.CONTROL CABINET 3
      TURN ON UPS CONTROL POWER (TOGGLE SWITCH)
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

TF AUX.CONTROL CABINET 4
       TURN ON UPS CONTROL POWER (TOGGLE SWITCH)
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

TF BYPASS CONTROL CABINET
      TURN ON UPS CONTROL POWER (TOGGLE SWITCH)
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

OH2U AUX. CONTROL CABINET
      TURN ON UPS CONTROL POWER (TOGGLE SWITCH)
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

OH2L AUX.CONTROL CABINET
       TURN ON UPS CONTROL POWER (TOGGLE SWITCH)
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

OH1  CROWBAR CABINET
      TURN ON UPS CONTROL POWER (TOGGLE SWITCH)

OH1 AUX. CONTROL CABINET
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

EF3 PLC SLIM MODULE
        TOGGLE SWITCH 01/11 AUX POWER ON
        TOGGLE SWITCH 03/13 RESET

EF3 POWER SUPPLY
        RESET BREAKERS ON KU401C MODULES
        CHECK CONRROL SWITCH IS IN REMOTE POSITION
        CHECK AUXILIARY SWITCH IS IN AUX ON POSTITION
        CHECK BACKUP TIMER IS SET TO 4.OO SEC

EF1 AUX. CONTROL CABINET
      TURN ON CONTROL XFMR POWER CB
        START HEAT EXCHANGER FAN
        PUSH RESET BUTTON

CHOPPER CONTROL PANEL
        TURN ON POWER
        TOGGLE SWITCH 00/10 RESET LOCATED ON TMX PLC RACK SIM MODULE
        VERIFY EFC CONTROL STATUS OF CHOPPER CONTROL LEDS
                (THE FOLLOWING LEDS SHOULD BE ON:
                        MOD1 DUMP COM. (2ND FROM TOP)
                        MOD4 DUMP COMM (1ST FROM TOP)
                        MOD4 INVERT P.S.(2ND FROM TOP)
                        MOD4 READY (3RD FROM TOP))

EF1 COMMUTATION SWITCH CONTROL CABINET
        TURN ON CB1 AND CB2

EF1 MASTER CONTROL CABINET
        TURN ON CONTROL POWER
        CHECK DUTY CYCLE AND PULSE DURATION TIMERS (003M & 035(0.1S))
        CHECK LOCAL/REMOTE SWITCH IS SET TO REMOTE

EF1 PLC RACK
        TOGGLE SWITCH 03/13 RESET

OH1 COMMUTATION SWITCH
        TURN ON CB1 AND CB2

OH1 MASTER CONTROL CABINET
        TURN ON CONTROL POWER
        CHECK DUTY CYCLE AND PULSE DURATION TIMERS (003M & 035(0.1S))
        CHECK LOCAL/REMOTE SWITCH IS SET TO REMOTE

OH1 PLC RACK
        TOGGLE SWITCH 03/13 RESET

TF MASTER CONTROL CABINET
        TURN ON CONTROL POWER
        CHECK DUTY CYCLE AND PULSE DURATION TIMERS (003M & 060(0.1S))
        CHECK LOCAL/REMOTE SWITCH IS SET TO REMOTE

TF PLC RACK
        TOGGLE SWITCH 03/13 RESET

OH2U MASTER CONTROL CABINET
        TURN ON CONTROL POWER
        CHECK DUTY CYCLE AND PULSE DURATION TIMERS (003M & 035(0.1S))
        CHECK LOCAL/REMOTE SWITCH IS SET TO REMOTE

OH2 COMMUTATION SWITCH
        TURN ON CB1 AND CB2

OH2L MASTER CONTROL CABINET
        TURN ON CONTROL POWER
        CHECK DUTY CYCLE AND PULSE DURATION TIMERS (003M & 035(0.1S))
        CHECK LOCAL/REMOTE SWITCH IS SET TO REMOTE

OH2 PLC RACK
        TOGGLE SWITCH 03/13 RESET
 
UPS POWER SUPPLY
        CHECK MESSAGES ON LCD SCREEN
        NOTE AN ERRORS
        NOTE LOAD PERCENTAGE

 OH1 COMMUTATION SWITCH
        PUSH RESET BUTTON 

 FINALLY CHECK
        MAKE ANOTHER PASS THROUGH THE POWER ROOM
        AND VERIFY ALL THE CABINET LIGHTS ARE ON.

SECOND POWER TURN-ON

OH1 SPELLMAN POWER SUPPLIES
        TURN ON POWER
        TURN ON HIGH VOLTAGE

OH2 SPELLMAN POWER SUPPLIES
        TURN ON POWER
        TURN ON HIGH VOLTAGE

EF1 SPELLMAN POWER SUPPLIES
        TURN ON POWER
        TURN ON HIGH VOLTAGE

PRIOR TO COMPLETING THE NEXT TWO STEPS
DON THE ARC PROTECTION CLOTHING LOCATED
IN THE LOCKER NEXT TO THE TF CABINET.  THE
ARC PROCTECTION EQUIPMENT THAT MUST BE
WORN INCLUDES A COAT, HARD HAT, SAFETY GLASSES,
FACE SHIELD AND GLOVES.

*********************************************************

480V POWER DISTRIBUTION CENTER
        CLOSE CBT 11 EF2U A, B
        CLOSE CBT 12 EF2L A, B
        CLOSE CBT 13 EF2L C, D
        CLOSE CBT 21 EFC A, B, C
        CLOSE CBT 22 EF2U C, D
        CLOSE CBT 24 CORRECTION COIL CABINETS

TMX POWER SUPPLIES
        PUSH RESET BUTTON
        CLOSE CIRCUIT BREAKER
        PUSH RESET BUTTON

*********************************************************