Bus Instrumentation Calibration 12/09/98 JHI Coil Resistance Measurements . verify that 5 amp bus fuses are installed and continuous on the 5 volts source supplies . verify that 1/2 amp bus fuses are installed and continuous on the voltage taps across the bus . turn on 5 volt supplies and verify readings at PLC Voltage Measurements . remove 1/2 bus fuses and apply +100, 0, and -100 volts with precision voltage source across the voltage tap leads . verify proper signal levels through data system Current Shunts . remove BNC cable from shunt . using precision voltage source apply +1, and -1 volts to the cable . verify proper signal levels through data system Bus Rogowski Coils . install leads across bus Rogowski to stepdown transformer . apply 500 to 700 amps through Rogowski at 60 Hz . verify proper signal level through data system . verify proper signal levels through to Hybrid computer MOV Rogowski Coils . install leads across MOV Rogowski to stepdown transformer . apply 500 to 700 amps through Rogowski at 60 Hz . verify proper signal level through data system Commutation Rogowskis . verify that leads to Rogowskis are okay . if okay then we will check during operation of the commutation supplies otherwise: . install leads across MOV Rogowski to stepdown transformer . apply 500 to 700 amps through Rogowski at 60 Hz . verify proper signal level through data system Ground Fault Fuses . verify the TF center tap ground is connected properly . verify that all fuses are continuous with an ohmmeter . pop each switch and verify that we get a ground fault alarm in the control room . verify fault propagates properly around the power room Ground Fault Current Pearson Transformers . use SCR to dump a 5 to 20 amp, 100 uS long pulse through each Pearson Transformer . measure current with shunt signal sent to data system . verify proper operation of transformers Reed Switches . use a small magnet to check that all the bus reed switches work properly and sound horn . check that MOV reed switches latch relays Hi-Yard and Alternator signals . 13.8kV Va, Vb, Vc . 13.8kV Ia, Ib, Ic . Alternator exciter current and voltage . Alternator field current and voltage . Alternator speed