Alcator C-Mod Run 1090819 Information

Back to runs

Miniproposals
Miniproposal:563
Date Filed: 7/30/2009
Title:Toroidal asymmetry of impurity seeding in support of ITER divertor gas injection requirements
First Author:Richard Pitts
Session Leader:Brian Labombard (shots 1-14)

Operators
Session leader(s):Brian Labombard
Physics operator(s):Steve Wolfe
Engineering operator(s):Bill Cochran,Gary Dekow

Engineering Operator Run Comment
automatically entered by signon - please replace with real comment

Session Leader Plans
Entered: Aug 19 2009 04:43:47:940PM
Author: Brian Labombard
Run Plan for 1090818

MP#563 "Toroidal asymmetry of impurity seeding in support of ITER divertor gas injection requirements"

Goal
We will attempt to finish up the ohmic L-mode density scan, dialing up some NL04 ~ 1.4e20 discharges.
If things go well, we will try adding ICRF power to see if toroidal variations in divertor radiation are affected.

Setup
NINJA should be filled to 12 PSI N2. Reload shot#1090814019.

Shot Plan

A. Set up 1.0 MA, 5.4 tesla, NL04 ~ 1.4e20 m-2
Take a shot without N2 injection.
Set up NINJA to puff N2 starting at 0.8 seconds for 0.2 seconds duration.
Verify that N diagnostic signals are good: Chromex, VUV, CXRS (NV)
Run through the capillary sequence (one shot for each):
K30-012
D30-012
H30-012
B30-012
F30-012
Take a shot without N2 puff.
Run through capillary sequence again (or a sparser set)

B. Add ICRF power at ~1 MW level. Compare K_BOT_10 response to puffing at K and B capillaries.
Compare 1MW power from D, E, J antennas

Physics Operators Plans
Entered: Aug 18 2009 05:56:29:190PM
Author: Steve Wolfe
-----------------
Engineering Setup
-----------------

Run begins at ? and ends at 17:00

Power systems as on: 1090814019

Acoil: +Dtop -Dbot -Jtop +Jbot (standard) Hybrid Enabled

Gas setup:

Fill B-Top with 6 psi D2 Hybrid enabled (PG4)
fill B-side lower with 1 psi Ar Hybrid DISABLED (PG1)
leave B-side upper as is Hybrid DISABLED (PG2)
fill B-main (C-side) with 40 psi D2 Hybrid enabled (PG3)
fill NINJA with 12psi N2 DISABLED

Enable gatevalves and shutters: ECE, VUV, Z-bolo

Torvac gatevalve toggle (yes/no): no

Boronization(yes/no): no
Overnight ECDC (yes/no): If we could, but doesn't look like we can

ICRF(yes/no): no
LH(yes/no): no
DNB(yes/no): no
Cryopump (yes/no): no

Vessel temperature: 35/35/35

------------------------------
ECDC Parameters (if requested)
------------------------------
gas and pressure: D2 at 2e-4 Torr
sweep: 44/45/103 cm
scan: 20/120 s

*********************************************
If we can run, it's supposed to be the remainder of MP#563 that didn't
get done last Friday. Start at nl04=1.4e20 as on 1090814019
and puff N2 from NINJA floor capillaries.

Session Leader Summaries
Entered: Aug 19 2009 08:58:37:940PM
Author: Brian Labombard
Run Summary for 1090819

MP#563 "Toroidal asymmetry of impurity seeding in support of ITER divertor gas injection requirements"

I suppose our luck had to run out sometime on obtaining a continuous string of nearly flawless discharges for this MP. After the TF scanner repair was completed at around 2:15 pm and a temperature control problem was fixed at A-port horizontal (causing a leak), things started to look good. Shot#5 was the discharge that we wanted to study (first plasma attempt). Shot#6 was a repeat (forgot to enable NINJA) and shot#7 was an N2 puff from a floor capillary. But then the wheels fell off the wagon. Shot #8 was a power supply dud, followed by 9 with no TF. Discharges after this were behaving as if out of control (see PO summary), suggesting that something is not right with a power supply control or two. It may be a rough start for the run tomorrow unless the gremlins can be found.

No data were collected in support of MP#563 today.

Shot log:
5 -LSN, 1.0 MA, 5.4T, NL04 = 1.4
no probes scanning

Next: puff N2 from K30-012

6 -LSN, 1.0 MA, 5.4T, NL04 ~ 1.4
ASP(+3) scanning 0.75, 1.1, 1.35
no NINJA puff. NINJA was not enabled on PLC.
ASP could be deeper

7 -LSN, 1.0 MA, 5.4T, NL04 ~ 1.4
ASP(+4) scanning 0.75, 1.1, 1.35
NINJA N2 527 torr, Trigger 0.8, Duration: 0.2
Capillary: K30-012, Torr-Liters: 4.3

8 - power supply dud

Change in plan. Go back to NL04 ~ 1.1 and then add ICRF.
Reload 1090814005. No NINJA.

9 - no TF

10 - Large early Marfe, disrupts at 0.57 s

11 - Early disruption

12 - no power shot

13 - reload of shot #7, LSN, 1.0 MA, 5.4T, NL04 ~ 1.4
disrupts at 1.27 s
No puff, no probes scanning.

14-fizzle

Physics Operator Summaries
Entered: Aug 19 2009 07:42:31:290PM
Author: Steve Wolfe
Physics Operator Summary for Wed, 19-Aug-2009

MP#563: Toroidal asymmetry of impurity seeding in support of ITER divertor gas
injection requirements 
SL: Labombard
PO: wolfe
EO: Cochran, Dekow

The run started late (over a day late in some accounting) following repairs to
the TF tap instrumentation that was damaged in the ground fault incident last
Friday. The connectors from the lower TF voltatge taps were removed from the
fuse box, individually wrapped, and bagged off. The connections from middle
and top taps were left connected, and the fuse boxes grounded. 

Megger hipot of the magnet to ground showed 2.5MOhms, unusually low. It is
believed (Gwinn) that this is due to ice and liquid water on the bus tunnel. 

Shot#1 was a successful scanner test of the remaining TF voltage taps. 
Shot#2 attempted a 10kA magnet test, but had an alarm indication due to
something not being reset in the bypass cabinet and had to be run as no-power;
shot#3 was a successful 10kA test, and shot #4 was successful 50kA TF
test, both under PLC control.

Before shot#5, an air leak opened up at A-port horizontal, due to a heater
being left off, which caused the port to freeze. Pressure in the torus rose to
the high five scale, then came back down to the 8 scale after the heat was
restored. 

Plasma operation began with shot#5, 1MA, NL04=1.4e20 baseline (no N2 puff)
shot based on 1090814019, which ran fine despite the air leak. We began a
sequence of toroidal variation of the N2 puff locattion under these
conditions: on #6 the NINJA wasn't enabled, so the first N2 puff was
#7. However shot#8 experienced an oh2l crowbar in pre-charge with lost fuses,
and we never really got back to decent plasmas.

Since there was not going to be sufficient time to complete a repeat scan of
the toroidal puff locations, even with the run extended to 18:00, the SL
decided to try to do the RF heated comparison (part B of the SL Plan) at least
with one antenna to scope out that aspect of the problem. Therefore I imported
segment 2 from 1090814005, the baseline for the nl04=1.1e20 part of the
experiment that was actually completed last Friday. 

However, after a no-TF dud on shot#9, shot#10 had a giant marfe and disrupted
early. All aspects of plasma control seemed to be poor on this shot, which
bore no resemblence to the source shot. The only change I had made other than
importing the segment 2 was to reduce the pg3 puff in seg1 to try to counter
an early marfe that appeared on shot#7. Among other symptoms on shot#10 was
the fact that the demand on EF4 was on the positive rail for essentially the
whole seg2 part of the shot, and the plasma was actualy pushed back onto the
inner wall (big clearin error). Thinking there might be a problem with the
imported segment (later PCS_compare indicated the programming was as expected,
just the density change and an irrelevant change in the TF rampdown time) I
re-imported seg2 from shot#7 and reduced the density there. Shot#11 also
disrupted around 0.5sec, but with differnt behavior. EF4 demand looked more
normal, but there were big vertical thrashes around .14sec and a killer vde
begining ~0.45sec. It is unclear why. All supplies seemed to be following
command, and there seemed to be no obvious errors in magnetics. 

Still thinking maybe something was broken in the pcs program, I reloaded the
entire shot#7, including the startup segment, and loaded it without
modification. By this time, SL had pretty much given up, and the only purpose
was to diagnose whatever was going wrong so maybe it could get fixed by
tomorrow.  Shot#12 had a computer problem (pcdaqeng1) resulting in critical
init failures. Shot#13 ran clean until about 1.2sec and then developed a vde,
although n/ncrit was only about 1.0. I couldn't see any evidence of a supply
not following demand, or of a magnetics error. 

Shot #14 was to be a repeat of #13 with the density again lowered to 1.1e20,
and it fizzled with Br0 running negative by 2mT. The major contributer seemed
to be oh2L which was over 1kA more negative than normal, actually running more
negative than oh2u, which is the opposite of the usual ratio. The oh2u and
ef2's were also significantly different. DPCS was commanding less negative
voltage on oh2l before t=0, the correct direction, and the supply was obeying,
according to the supply voltage trace. It actually looked like oh2l had
followed the voltge commands all through pre-charge, unlike OH2u which was
doing its usual behavior of saturating on a demand above -100V between -.8 and
-.3sec. However, the current was getting out of range, and the bus voltage
trace appears to be about 25V more negative than the supply voltage. This
could be a problem in the supply. I've sent email to Bill and Gary to
investigate this. 

In the end, no useful data were obtained for the MP today. I suppose we should
be happy that we sort of got back into operation after the ground fault
incident, and we'll hope for better tomorrow. 

Scorecard:
---------

        Tests/No Power       5
	Duds                 2 (1TF, 1 OH2L)
	fizzles              1
        Plasmas              6 (2 early disruptions, 1 flattop disruption)
       ========             ==
        Shots               14


       

Session Leader Comments
Aug 19 2009 03:00:49:743PM1090819005Brian Labombard5 -LSN, 1.0 MA, 5.4T, NL04 = 1.4
no probes scanning

Next: repeat and puff N2 from K30-012
Aug 19 2009 03:21:49:140PM1090819006Brian Labombard6 -LSN, 1.0 MA, 5.4T, NL04 ~ 1.4
ASP(+3) scanning 0.75, 1.1, 1.35

no NINJA puff. NINJA was not enabled on PLC
Aug 19 2009 03:25:33:690PM1090819007Brian Labombard7 -LSN, 1.0 MA, 5.4T, NL04 ~ 1.4
ASP(+4) scanning 0.75, 1.1, 1.35
NINJA N2 527 torr, Trigger 0.8, Duration: 0.2
Capillary: K30-012, Torr-Liters: 4.3
Aug 19 2009 04:12:41:177PM1090819008Brian LabombardChange in plan. Go back to NL04 ~ 1.1 and then add ICRF after a few shots.
Reload 1090814005. No NINJA
Aug 19 2009 04:42:04:033PM1090819010Brian Labombard10 - Large early marfe, disrupts at 0.57 s
Aug 19 2009 05:51:18:747PM1090819013Brian Labombard13 - reload of shot #7, LSN, 1.0 MA, 5.4T, NL04 ~ 1.4
disrupts at 1.27 s
No puff, no probes scanning.

Physics Operator Comments
Aug 19 2009 08:28:22:570AMSteve Wolfe
Setting up for plasma run, just in case.
Load from 1090814019, no changes
Load at 19-Aug-2009 08:28:13.00
Open tree /home/wolfe/pcs_scratch      -1
Open tree done
 

Aug 19 2009 10:02:39:933AMSteve Wolfe
We are presently planning to start magnet tests at noon and plasma operation
at 13:00. Stay tuned.

Aug 19 2009 01:43:53:713PM1090819001Steve Wolfe
Shot#1: No power test of TF scanner. 
As expected the inside and bottom are missing
There seem to be low values (normal?) on these at turns 64,65
or so that I don't understand. These are in the bundle that
probably includes the ground, but the bottom is still disconnected for
those as well. The ground connection is supposed to be at turn 60.

There is a large value on TOP turn 1, not sure why. 

Aug 19 2009 01:52:15:373PM1090819002Steve Wolfe
Shot#2: 10ka magnet test 
alarm on bypass, do not excite alternator
do no power. 

Aug 19 2009 02:05:30:957PM1090819003Steve Wolfe
Shot#3: 10ka magnet test 
Got 9kA, looks ok. 
No gf

Aug 19 2009 02:17:19:210PM1090819004Steve Wolfe
Shot#4: 50ka magnet test , PLC control
ran ok, no faults, 
We're good to go. Cell access for Rick, and 
final inspection of tf cables.

Aug 19 2009 02:30:04:107PM1090819004Steve Wolfe
Shot#5: Plasma attempt:1MA, 1.4e20
Raise pg4 from 18 to 20msec; 
igt=6.2e-8, we've had no ecdc since Friday AM. 
 We've got an air leak in progress
Brian - you're under a curse. Go sacrifice a chicken.

Aug 19 2009 02:58:26:370PM1090819005Steve Wolfe
Shot#5: Plasma attempt:1MA, 1.4e20
Raise pg4 from 18 to 20msec; 
igt=6.2e-8, we've had no ecdc since Friday AM. 
 We've got an air leak in progress
Brian - you're under a curse. Go sacrifice a chicken.

The leak was apparently at a-port due to an ice-up; heater
was off. We got up to the high e-5 scale, back down to mid-8's now.
Give it a try, see how dirty it is. 
 plasma! full length. Density looks right, 
2pi foil is 750kW, if it's right. Matt is doing a cell access, not sure why.
Startup looks decent, no runaways. 

Next: no changes, Brian will puff N2

Aug 19 2009 03:10:41:980PM1090819006Steve Wolfe
Shot#6:  no changes, Brian will puff N2
IGT=1.3e-6 in INIT
plasma full length, no runaways, 
Startup still ok
Brian didn't puff. I guess its another baseline.

Next: enable ninja and try again

Aug 19 2009 03:23:47:173PM1090819007Steve Wolfe
Shot#7:  no changes, Brian will puff N2
plasma, looks like a marfe early, no runaways, 
disrupts in rampdown 1.75sec
Note that I'm not making any changes, but Earl's routine is 
reporting changes in currents at the .7% level, not sure why.

Next: decrease pg3 in seg1 to try to suppress marfe

Aug 19 2009 03:38:05:290PM1090819008Steve Wolfe
Shot#8: decrease pg3 in seg1 to try to suppress marfe
Ignore the little disruption on previous shot
Brian is puffing from a different cap.
PF breaker tripped during init -- DUD
OH2L crowbars

Aug 19 2009 04:07:28:783PM1090819009Steve Wolfe
Shot#9: decrease pg3 in seg1 to try to suppress marfe on #7,
no other changes to startup,but it looks like we're going to change
the plan and do the RF part of the experiment at lower density 
import seg2 from 1090814005 NL04=1.1e20. This will be a baseline
so no rf, no N2 puff



Aug 19 2009 04:18:16:977PM1090819009Steve Wolfe
Shot#9: decrease pg3 in seg1 to try to suppress marfe on #7,
no other changes to startup,but it looks like we're going to change
the plan and do the RF part of the experiment at lower density 
import seg2 from 1090814005 NL04=1.1e20. This will be a baseline
so no rf, no N2 puff

No TF. Dud. Find that chicken yet, Brian?

Aug 19 2009 04:51:32:443PM1090819010Steve Wolfe
Shot#10: Another try at 1.1e20 baseline
Early disruption, huge marfe, disrupts at .57sec
Big early thrash on zcur, almost lost it then. 

I have no idea what happened on this shot. Looks like ef4 is flatout. 
Re-import from 1090819007 and just change the density

Aug 19 2009 06:10:15:487PM1090819010Steve Wolfe
Shot#10: The differences between shot 10 and shot 7 in PCS were 
basically the expected ones, namely the density and the pg3 in seg1.
There is also a late change in the TF current rampdown, which didn't 
get reached. I do not understand the reason for the max demand on 
ef4 voltage in shot#10. The main demand is probably ef2byef4, which 
is 2000 Amps error. This was not the case on the source shot 1090814005.
Possibly it is all caused by the monster marfe on this shot. So why did
that happen? There was a big early marfe on 1090814005, like the one
I was trying to get rid of by reducing the pg3 in seg1 on shot#10. There
was also a runaway problem. 
 

Aug 19 2009 05:21:21:813PM1090819011Steve Wolfe
Shot#11: Re-import from 1090819007 and just change the density
Disrupts at 0.5sec big vertical thrashes. This time the EF4 voltage
doesn't rail, but something is wrong. This one doesn't have the early
marfe either, but it almost loses vertical position at .14sec, 
then goes vertically unstable at .45sec for no obvious reason.


 

Aug 19 2009 05:28:04:177PM1090819012Steve Wolfe
Shot#12: Reload shot#7 and see if it runs. I think there is something
broken, but I can't tell what. 
Got critical failure in init, something wrong on pcdaqeng1

No power shot

 

Aug 19 2009 05:48:17:353PM1090819013Steve Wolfe
Shot#13: Reload shot#7 and see if it runs. 
plasma to 1.3sec, supplies look ok until it goes vde
n/nc=1.0, shouldn't be unstable. 
 

Aug 19 2009 06:42:49:690PM1090819014Steve Wolfe
Shot#14: Decrease nl04 demand to 1.1 just to see if we can get it to go
through. 

Fizzle. Br0 went much more negative on this one, Earl
points out that oh2l is much more negative on this shot. There are
also differences on the oh2u and ef2's. However, while oh2l is normally
less negative than oh2u, on this shot the opposite is true. 

Br0 error is positive by 2mT in phys_aout, has been being right at zero.
This implies a power supply not following demand, or not catching up 
with demand. However, the voltage traces don't bear this out, they look
pretty close from -.3 to 0. However, the demand on oh2l is near 0V
while normally it is -25V or so. This implies an earlier deviation that is
not being fully compensated. It's not so obvious when this happens though

Engineering Operator Comments
ShotTimeTypeStatusComment
101:27:06:990PMTestOkTF Scanner Test
201:48:50:387PMTestBadTF Type 3 Flt
302:00:31:110PMTestOkTF PLC 10KA Test
402:10:42:630PMTestOkTF PLC 50KA Test
502:52:22:350PMPlasmaOkNo Faults
603:05:09:293PMPlasmaOk
703:17:37:720PMPlasmaOk
803:32:32:350PMPlasmaBadOH2L Commutation Fault
904:15:03:413PMPlasmaOk
1004:33:56:280PMPlasmaOk
1104:54:23:880PMPlasmaOk
1205:24:23:283PMPlasmaBadpcdaqeng1 problems
1305:38:24:350PMPlasmaOk
1405:52:33:370PMPlasmaOk

System Availability
Aug 19 2009 01:26:41:207PM
SystemAvailableCommentAvailability
Changed
OwnerDescriptionWho Can
Change
Active MHDnosecured - tagged outJun 02 2008 11:03AM (sears)Joe SnipesActive MHD Antennasears,snipes
BESyes7 horizontal views spread out R_maj=[0.72-0.9m], 3 cm over the tokamak midplane (beam) Jul 09 2009 05:12PM (bespam)Bill RowanBeam Emission Spectroscopybespam,liao,rowan
Bolometersyes2pi (diode+foil), AXA, AXJ, WB3AX, WB4AX, LEDGE-AX working fine. MID/LEDGE/DIV foils still need calibrations appliedJul 28 2009 09:59AM (mlreinke)Matt ReinkeBolometershutch,mlreinke
BoronizationnoBottle Removed from the Cell, Piezo box on Igloo Removed. System in safe mode for In-Vessel AccessMay 30 2008 02:25PM (dekow)Jim IrbyBoronizationdekow,irby
CNPAnoSingle channel CNPA available as of 12/1707Jun 10 2009 10:22AM (twf)Ron ParkerCompact Neutral Analyzerparker
Cryopump - Upper DivertornoCyopump hardware is not yet reinstalled in the cell.Jul 14 2009 09:21PM (labombard)Brian LaBombardUpper Divertor Cryopumpirby,labombard
CXRSyesThe wide-view toroidal array was installed, spatially and absolutely calibrated. There are 7 toroidal chords intersect the beam at the major_R_range=[74.2:83.6]cm. Spatial resolution: 1.2 cm. The F-top wide-view poloidal array was installed and spatially calibrated. There are 19 chords intersect the beam at the major_R_range=[0.65:0.9.]m. Spatial resolution: 1.22 cm.Jul 09 2009 05:16PM (bespam)Bill RowanCharge Exchange Spectroscopybespam,blip,liao,rachmcd,rowan
D Alphayes\ha2_bright is available; \SPECTROSCOPY::TOP.VUV.VIS_SIGNALS:MCP_VIS_SIG1 is not availableJul 01 2009 09:45AM (terry)Jim TerryBalmer Alpha Monitorirby,terry,wolfe
Dalsayessystem is aligned and operating; not yet calibratedJul 14 2009 02:22PM (marmar)Earl MarmarVisible Bremsstrahlungmarmar
Disruption Mitigationnosafely disabled; ready to be dismantledMay 28 2008 10:22AM (granetz)Robert GranetzGas Jetgranetz,whyte
Divertor IRno Mar 06 2007 10:50AM Glen WurdenDivertor IR Digital Videogwurden,terry
Divertor IR Spectroscopyno Mar 06 2007 10:51AM Glen WurdenDivertor IR Spectroscopygwurden,terry
DNBnopower locked & tagged out; gate valve disabledMay 28 2008 10:03AM (granetz)Robert GranetzDiagnostic Neutral Beamdterry,granetz,gung
ECDCno6/10/09 Magnetron relocated to west wall in cell at H-port. All controls and hardware have been installed but need to be tested prior to full operation. Magnetron Unplugged and Red tagged, PEI breaker red tagged, Safe for In-Vessel ActivityJun 10 2009 02:35PM (dekow)Jim Irby2.45 GHz, 3 kW, discharge cleaning systemdekow,irby,pfeiffer
FRC-ECEyesThe lower freq. 16 channels are ready. Still need calibration and signal level adjustmentsJul 14 2009 12:15PM (phillips)Perry PhillipsHeterodyne ECE-32 channelsphillips
G-Side RatiomaticyesGauge installed. Problem with controller - signal noisy.Jul 14 2009 09:11PM (labombard)Brian LaBombardG-side ratiomatic ionization gaugelabombard,toland
Glow Dischargeno6/10/09: Paddles meggered at 1000 v to machine ground (>300 Mohm) prior to closing the vacuum chamber. Plugs for Power Supply and Controls Unplugged and Red Tagged, Safe for In-Vessel AccessJun 10 2009 01:47PM (dekow)Jim Irby1 kV, 5 A, glow discharge systemdekow,dterry,irby
GPCyesOperational.Jul 28 2009 04:23PM (hubbard)Amanda HubbardECE Polychromaterhubbard,schmidt
GPC2yesMost channels operational.Jul 28 2009 04:23PM (hubbard)Amanda HubbardECE Polychromaterhubbard,schmidt
GPIyesThe Xpt-view, the midplane-view cameras are operational. The innerwall GPI (coupled to the fast-diodes) is available. Jul 01 2009 09:45AM (terry)Jim TerryGas Puff Imagingterry,zweben
H/Dyesposes no safety hazard for people working around the machineJun 18 2009 01:04PM (marmar)Earl MarmarH/D Ratiomarmar
HEATnoDisconnect switch is open, reg tagged and locked. Shunt Trip Breaker is opened. Safe for in-vessel work.Jun 04 2008 12:24PM (dekow)Gary Dekow - Machine Heaters -burke,dekow
Hirex JryesHirex-Jr has been installed and testedJun 17 2009 11:54AM (rice)John RiceHigh Resolution X-Rayince,rice
Hirex Sryescurrently only one detector is operational, off-axis He-like argon emissionJul 14 2009 10:01AM (rice)John RiceHigh Resolution X-Rayince,rice
HXRnoIn safe mode (high voltage turned off)May 27 2008 09:19PM (schmidt)Ron ParkerHard X-Ray Arrayparker,schmidt
ICRF D-Antennayesoperational at 80 MHzJul 21 2009 04:49PM (wukitch)Steve WukitchD-port antennawukitch,ylin
ICRF E-Antennayesantenna and FFT operationalJul 21 2009 04:49PM (wukitch)Steve WukitchE-port antennawukitch,ylin
ICRF J-Antennayesavailable for conditioning and testingJul 21 2009 04:50PM (wukitch)Steve WukitchJ-port antennawukitch,ylin
Lower HybridnoBreaker locked and tagged out. Waveguide disassembly started. Open Waveguides have been shorted.May 28 2008 09:47AM (dterry)Ron ParkerLower Hybriddterry,parker,wallaceg
LPInoBeam line removedMay 30 2008 02:09PM (bose)Earl MarmarLithium Pellet Injectorbose,marmar
Ly-alphayesMidplane, WB4-LY, LEDGE-LY all collecting data but processed data not in tree. WB1-LY not attached.Jul 07 2009 01:01PM (mlreinke)Matt ReinkeLyman alpha cameraslabombard,mlreinke
McPhersonyesCollecting spectra but control system problem is not reporting voltages to treeJul 28 2009 10:00AM (mlreinke)Jim TerryVUV Spectrometermlreinke,terry
MichelsonyesOperational. Recalibrated 7/27/09.Jul 28 2009 04:22PM (hubbard)Amanda HubbardECE Te Profileshubbard,schmidt
MKSyesGauges are on. B-bottom is not operating - bad sensor head?Jul 14 2009 09:12PM (labombard)Brian LaBombardBaratron pressure gaugeslabombard
MLPnoSystem is in edge lab. Version 2 drivers ready to test. Needs a student to help work on it.Jul 14 2009 09:20PM (labombard)Brian LaBombardMirror Langmuir Probe Electronics Systemlabombard
MSEnoAs of 6/10/09, MSE is calibrated & ready to go. Awaiting DNB.Jun 10 2009 10:34AM (sscott)Steve ScottMotional Stark Effectjinseok,sscott
NeutronsyesNeutron detectors are calibrated and ready to go. Voltages will be turned on prior to first plasma.Jun 10 2009 10:35AM (fiore)Catherine FioreNeutron Detectorsfiore
Neuts and HardsyesOperational --- Uncalibrated and needs to be positioned at portJun 25 2009 05:08PM (irby)Jim IrbyX-Ray/Neutron Detector at K-Horirby
NINJAnoCapillaries were tested in-vessel. Plenum has a leak and needs fixing.Jul 14 2009 09:14PM (labombard)Brian LaBombardNINJA gas pufflabombard,terry
PCIyesSystem is operable. Channels 7 and 9 (of 32) are dead.Aug 05 2009 02:48PM (edlund)Miklos PorkolabPhase Contrast Imagingarai,edlund,ennever,ntsujii,porkolab
Penning GaugesyesHigh voltage is enabled (on during INIT, off during RECOOL).Jun 30 2009 09:42PM (labombard)Brian LaBombardPenning Ionization Gaugeslabombard
Plasma TVyesWIDE1, WIDE2 (chan 33), DANT, JANT and DIV are operational.Jul 01 2009 09:46AM (terry)Jim TerryVideo of plasma via several camerasdekow,irby,terry,wolfe
PolarimeternoSafe for Machine EntrySep 14 2007 12:17PM (irby)Jim IrbyC-Mod Polarimeterirby
Power - Alternator Air SwitchyesChecked and Operational as of 06/18/09Jun 19 2009 08:04AM (irby)Gary Dekowfeeds all the other suppliescochran,dekow,dterry,irby
Power - PEIyesOperational ---- ECDC running as required Jun 19 2009 08:06AM (irby)Gary DekowPEI Systemcochran,dekow,dterry,irby
Power - TMXyesChecked out and ready for Magnet Tests as of 06/18/09Jun 19 2009 08:07AM (irby)Gary DekowEf2s,. EFCs and A-Coilsbyford,cochran,dekow,dterry,irby
Power SystemsyesChecked out and ready for Magnet Tests as of 06/18/09Jun 19 2009 08:07AM (irby)Jim IrbyC-Mod Magnet Suppliesbyford,cochran,dekow,dterry,irby
Probe Array - ISDyesArray is operational with new cPCI data system. Probe 14 has open circuit.Jul 14 2009 09:17PM (labombard)Brian LabombardInner Lower Divertor Probe Arraylabombard
Probe Array - LHnoLH launcher not installed. Cables are unplugged at the A-port rack.Jul 14 2009 09:16PM (labombard)Brian LaBombardLower Hybrid Probe Arraylabombard
Probe Array - OSDyesArray is operational with new cPCI data system.Jul 14 2009 09:16PM (labombard)Brian LaBombardOuter Lower Divertor Probe Arraylabombard
Probe Array - UDIVyesArray is operational with new cPCI data system. Probe 13 has a bad cable (open).Jul 14 2009 09:17PM (labombard)Brian LaBombardUpper Divertor Probe Arraylabombard
ReflectometeryesAs of 7/21/09, all channels are operational (50, 60, 75, 88, 88usb, 88lsb, 110, 140 and 110-140 swept frequency)Aug 04 2009 11:20AM (dominguez)Earl MarmarReflectometerdominguez,marmar
Scanning Probe - ASPyesProbe is operational. Needs plasma conditioning.Jul 14 2009 09:18PM (labombard)Brian LaBombardA-Port Scanning Probelabombard
Scanning Probe - FSPyesProbe is operational. Needs plasma conditioning.Jul 14 2009 09:18PM (labombard)Brian LaBombardF-Port Scanning Probelabombard
Scanning Probe - WASPyesSystem connected to A-port WASP. Needs plasma testing.Jul 14 2009 09:19PM (labombard)Brian LaBombardInner Wall Scanning Probelabombard,nsmick
SparkeryesSparker now at K-Hor. Set for 100 uA of current. Will up to 200 uA before first plasmaJun 18 2009 01:01PM (irby)Jim IrbyField Emission Preionization for C-Moddekow,irby,parkin
TCIyesSystem restarted and aligned. Several chords available including NL04. Density Feedback available. Ready for plasma.Jun 18 2009 09:15AM (murray)Jim IrbyTwo-Color Interferometerirby,murray
TS - Coreyes2 lasers working. 15 spatial channels operational. Initial (NOT final) Te calibration applied. ***No ne calibration yet*** Aug 05 2009 08:44AM (jwhughes)Jerry HughesCore Thomson scatteringjwhughes,yma,zhang
TS - EdgeyesOperational, Te calibration is thought to be good. Density is ***uncalibrated***Aug 11 2009 02:31PM (jwhughes)Jerry HughesMillimeter resolution edge Thomson scatteringjwhughes,yma,zhang
Vispecno350 and 670 nm, 4 spatial channelsNov 28 2007 09:58AM (agraf)Alex GrafVisible Spectrometeragraf
XTOMOyescables attached, DAQ test run, ready for first plasmaJun 17 2009 03:42PM (mlreinke)Bob GranetzX-Ray Tomographygranetz,mlreinke