| Miniproposals | ||||||||||
|
| Operators | |
| Session leader(s): | Geoff Olynyk |
| Physics operator(s): | Bill Rowan |
| Engineering operator(s): | Andy Pfeiffer,Roza Tesfaye,Gary Dekow |
| Engineering Operator Run Comment |
| MP 714 MHD effects on massive gas injection disruption mitigation SL: Ol |
| Session Leader Plans |
| Entered: Aug 1 2012 04:19:47:670PM |
| Author: Geoff Olynyk |
Session leader plan for run 1120802 (Thursday, August 2, 2012) MP 714 - "MHD effects on massive gas injection disruption mitigation", run 1 of 2. G.M. Olynyk Objectives:
Gas request:
Diagnostics & systems requested:
Important note for diagnosticians: After disruption mitigation gas jets are fired, torus pressures can rise as high as 1 torr. Although, we will only fire a single gas jet on this day and so it shouldn't go above 500 mtorr. If you have sensitive diagnostics, these should have their protective gate valves closed. PhysOp instructions: Nearly every shot today has a different elongation, density (nl04), and field. Table to be given to PhysOp by Session Leader with list of shots, and guidance to be given throughout the day. Other instructions (Session Leader, auxiliary systems, diagnostic setup, etc.):
Run plan:
The reason for the twice-through scans of elongation and safety factor is that in the past, we have seen variablity in the mitigated disruptions even given identical target plasmas. We want to have at least two mitigated disruptions into each target here to se if this is still the case. It is noted that this plan comprises 19 useful shots, plus any required for discharge development. Given the long inter-shot wait time on gas jet shots, plus the extra-long wait time on the 7.0 T shots, this is an ambitious plan. We hope to be able to accomplish the majority of the run plan. |
| Entered: Aug 1 2012 04:23:51:967PM |
| Author: Geoff Olynyk |
Here is the planned list of shots (screenshot from spreadsheet) as of 4:25 pm on 2012-08-01.
![]() |
| Entered: Aug 1 2012 06:43:49:870PM |
| Author: Geoff Olynyk |
| *** Please note that today's run will have some shots at 7.0 T, which I understand counts as "high field" from an operational standpoint. *** |
| Physics Operators Plans |
| Entered: Aug 1 2012 02:39:40:357PM |
| Author: Bill Rowan |
| PhysOp Plan for Run 1120802
MP 714 MHD effects on massive gas injection disruption mitigation SL: Olynyk PO: Rowan PO Plan is to follow the SL shot list. ----------------- Engineering Setup ----------------- Run begins at 09:00 and ends at 17:00 Power systems as on: 1090911018 ** But set Fizzle Detector Gate Off time to 2.1sec, extend OH1, OH2U and OH2L invert times to 2.3 seconds, if not already set there. Acoil: +Dtop -Dbot -Jtop +Jbot (standard) Hybrid Enabled Gas setup: Fill B-Top with 6 psi D2 Hybrid enabled (PG4) fill B-side lower with 1 psi Ar Hybrid DISABLED (PG1) leave B-side upper as is Hybrid DISABLED (PG2) fill B-main with 40 psi D2 Hybrid enabled (PG3) leave H-bot as is Hybrid DISABLED (PG5) fill NINJA with 10 psi D2 DISABLED Enable gate-valves and shutters: ECE, VUV, HiREX Sr, Xeus/LoWEUS Leave z-bolo shutter as is (should be open) Torvac gatevalve toggle (yes/no): no Boronization(yes/no): no Overnight ECDC (yes/no): YES ICRF(yes/no): YES, 1 MW from E-antenna, transmitter #2 LH(yes/no): no Cryopump (yes/no): no DNB (yes/no): no Vessel temperature: 35/35/35 ------------------------------ ECDC Parameters (if requested) ------------------------------ gas and pressure: D2 at 2e-4 Torr sweep: 44/45/103 cm scan: 20/120 s |
| Session Leader Summaries |
| Entered: Aug 2 2012 06:00:35:990PM |
| Author: Geoff Olynyk |
| Session leader summary for run 1120802
Thursday, August 2, 2012 MP 714 - "MHD effects on massive gas injection disruption mitigation" (run 1 of 2) G.M. Olynyk
After a somewhat rocky start with data system problems (and one gas jet
system failure due to the interlock box), we had a fantastic run day,
completing the SL_PLAN by about 3:15 pm. Despite odd voltage transients on some
of the TF power supplies, the machine behaved flawlessly, with no lost shots
due to power systems issues.
After a single shot with our 5.6 T, 1.0 MA lower single-null baseline to shake
down the gas jet system and compare to previous gas jet disruption mitigation
runs, we did a scan of elongation in the inner-wall limited configuration. This
was a five-point scan, covering kappa = 1.01, 1.10, 1.30, 1.50, and 1.60. In
all cases, we fired the B-jet only, at t = 1.000 s. The gas jet system
was very reliable after the single interlock-box failure on shot 004.
Then, we covered a four-point scan of safety factor (by varying field at
constant plasma current) in the lower-single-null diverted configuration. By
using toroidal fields of 4.0, 5.0, 6.0, and 7.0 T, we covered a range of q*
from 3.36–5.87 (q95 from 3.51–5.56).
Both of these scans were then repeated, in order to quantify the variation in
toroidal radiation asymmetry (and other disruption parameters) with identical
target plasmas. We know that there is a large variation in the high-elongation
diverted plasmas, and wanted to see if this was true for the low-elongation
limited plasmas as well.
All of these scans were done at a constant current of 750 kA so that the energy
available to the disruption (~L*I^2) was constant. Also, by
keeping the current constant, the Greenwald density was constant. We also kept
the line-averaged density (nebar) as constant as possible (varying nl04 as we
changed the elongation), so the Greenwald fraction was also constant through
these scans.
With the SL_PLAN complete, we were able to do some of the shots that were
planned for the second run day, firing both gas jets using optimum timing into
limited plasmas at low, medium, and high elongation.
Finally, at the very end of the day, we tried one shot that was not planned at
all: We fired a single gas jet (the B-port jet) into a locked mode. This was
done as an exploration of whether the (2,1) mode, if present, might grow
quickly and make the thermal quench radiation more symmetric. One could
conceive of ITER or a reactor using non-axisymmetric coils to induce a (2,1)
mode just before, or as, the gas jets are fired for disruption mitigation!
Physics Operator Bill Rowan did a fantastic job of creating our unusual
low-elongation inner-wall limited plasmas. It also helped that we had target
shots from the MP 604 run ("Effect of elongation on the generation of
disruption runaway electrons using LH-driven seed") on 2010-09-08 for the
low-elongation limited plasmas.
Pumpdown after gas jet firings seemed to be proceeding more quickly today than
usual. Shot cycle times were just above 15 minutes on average, although at one
point we took a shot too quickly and had a fizzle. Later in the day, we were
closer to about 17 or 18 minutes between shots. Even on the high-field shots,
magnet cooling was not the defining factor in the inter-shot times, probably
because the induced disruptions meant that the field ramped down early.
A preliminary glance at the toroidal radiation asymmetry data indicates that
the disruptions (thermal quench and current quench) are very symmetric for
mitigated disruptions in low-elongation inner-wall limited plasmas. This
comports well with the hypothesis, based on the magnetic growth rates from run
1100908, that these (nearly) circular limited plasmas have fast n=1
growth rates, and thus low radiation asymmetry.
I have a lot of very good data to analyze from today. I think that the evidence
for the link between MHD and toroidal radiation asymmetry in mitigated
disruptions is getting stronger, and the key now is to figure out what's going
on and publish it ASAP.
Lessons learned: - Shot cycle can be as little as 15 minutes if Session Leader and Physics Operator are disciplined, and we only fire one gas jet (raising torus pressure to about 300 mtorr). It's longer, more like 18 minutes, if both gas jets are fired and the F-jet doesn't run away. - The B-port gas jet (our OLD gas jet) continues to run reliably and consistently. With a pulse duration of 1.41 ms, it consistently injects about 1300 torr-l (according to the B-side bottom MKS pressure gauge). - The F-port gas jet, on the other hand, is much less consistent. With a drive current pulse duration of 2.50 ms, the pressure pulse produced is anywhere from 2.5 to 15 ms long (although we didn't get the 15 ms "runaway" pressure pulses today). It really needs to be serviced/rebuilt by ORNL. If only we had more time... - The torus pressures after firing the gas jet according to the thermocouple gauge are consistently about 30% lower than the readings on the B-bottom MKS gauge. The thermocouple gauge is calibrated with hydrogen, though, and so one would not expect the calibration to be exact in this argon–helium mixture that we use for disruption mitigation. - The thermocouple gauge seems to saturate at very high torus pressures (above 1 torr). We didn't reach these pressures today, though. Shot summary: The problematic part of the day: 001 - No-power shot due to data system problems 002 - No-power shot due to data system problems 003 - Data system test 004 - Plasma, but gas jet didn't fire (interlock box failure) SL_PLAN part 1: 005 - Plasma and gas jet fired. This is our baseline (5.6 T, 1.0 MA LSN). SL_PLAN parts 2–3: 006 - Good plasma, good gas jet. Kappa = 1.30 007 - Good plasma, good gas jet. Kappa = 1.50 008 - Good plasma, good gas jet. Kappa = 1.60 009 - Good plasma, good gas jet. Kappa = 1.10 010 - Good plasma, good gas jet. Kappa = 1.03 SL_PLAN part 4: 011 - Good plasma, good gas jet. Bt = 4.0 T 012 - Good plasma, good gas jet. Bt = 5.0 T 013 - Good plasma, good gas jet. Bt = 6.0 T 014 - Good plasma, good gas jet. Bt = 7.0 T SL_PLAN part 5: 015 - Good plasma, good gas jet. Kappa = 1.30 016 - Good plasma, good gas jet. Kappa = 1.50 017 - Good plasma, good gas jet. Kappa = 1.10 018 - Good plasma, good gas jet. Kappa = 1.01 019 - Good plasma, good gas jet. Kappa = 1.60 SL_PLAN part 6: 020 - Good plasma, good gas jet. Bt = 4.0 T 021 - Good plasma, good gas jet. Bt = 5.0 T 022 - Fizzle. Gas jet still fired. 023 - Good plasma, good gas jet. Bt = 6.0 T 024 - Good plasma, good gas jet. Bt = 7.0 T High-elongation, definitely limited: 025 - Plasma, gas jet fired successfully, but still dithering between limited and diverted 026 - Good plasma, good gas jet. Kappa = 1.57 Elongation scan with two gas jets (bonus): 027 - Good plasma, kappa=1.01, both gas jets fired 028 - Good plasma, kappa=1.30, both gas jets fired 029 - Good plasma, kappa=1.57, both gas jets fired Firing single gas jet into locked mode (bonus): 030 - Good plasma (locked mode), B-jet fired successfully |
| Physics Operator Summaries |
| Entered: Aug 3 2012 07:55:30:167AM |
| Author: Bill Rowan |
| The run was in support of MP 714 "MHD effects on massive gas injection disruption mitigation" with SL Geoff Olynyk. Requirements for C-Mod operation included an elongation scan for a limited discharge and a q scan for a diverted discharge. Every shot included one or two massive gas injections. The run proceeded more quickly than expected, and the SL supplemented the plan by repeating some shots for statistics, adding a second massive gas injector (most of the shots used a single gas injector), and by adding a locked mode discharge.
The first shot was a lower single null based on 1120622012. Breakdown-and-ramp-up was taken from 1120731028. Taking the latter from the day previous to this run would not have been wise because of the segment 1 changes that were made. The resulting shot was used later in the run as a starting point for a q scan. The reference shot for the elongation scan for a limited discharge was 1100908011. Clearin was used to vary the elongation. Run 1100908 contained some guidance for correlation of clearin with elongation. The elongation was varied from 1 to approximately 1.6. Efit suggested that a lower x-point formed intermittently at the highest elongation. The elongation was reduced in tiny steps to remove the x-point. The first shots of the day were not successful due to computer problems. Score card 25 plasmas 01 fizzle 04 engineering shots ----- 30 total |
| Session Leader Comments | |||
| Oct 1 2012 06:58:16:627PM | Geoff Olynyk | Here are the shots used for the kappa (elongation) scan. All were at a plasma current of 750 kA.
shot kappa Btor nebar Wth q ---------------------------------------------- 1120802010 1.0 6.9 1.37 31 3.45 1120802018 1.0 6.9 1.50 39 3.45 1120802009 1.1 6.3 1.44 32 3.57 1120802017 1.1 6.3 1.59 32 3.60 1120802006 1.3 5.2 1.46 30 3.59 1120802015 1.3 5.2 1.69 29 3.67 1120802007 1.5 4.3 1.60 24 3.77 1120802016 1.5 4.3 1.55 24 3.70 1120802008 1.6 4.0 1.59 23 3.79 1120802026 1.6 4.1 1.59 25 3.85 | |
| Oct 1 2012 08:56:05:053PM | Geoff Olynyk | Here are the shots used for the single gas jet safety factor scan on run 1120802. Plasma current was constant at 750 kA; toroidal field was varying. Configuration was ordinary LSN diverted with elongation of about 1.58.
shot q* q95 Btor nebar Wth ------------------------------------------------ 1120802011 3.4 3.46 4.08 1.40 22 1120802020 3.4 3.50 4.08 1.50 26 1120802012 4.2 4.28 5.03 1.59 28 1120802021 4.2 4.26 5.03 1.56 25 1120802013 5.0 5.03 5.96 1.57 29 1120802023 5.0 4.93 5.96 1.61 24 1120802014 5.9 5.58 6.89 1.56 22 1120802024 5.9 5.56 6.90 1.58 20 | |
| Aug 2 2012 08:35:17:987AM | 1120802001 | Geoff Olynyk | Shot 1 - we are attempting to run an identical shot to 1120622012 (5.6 T, 1.0 MA).
Also - apparently we are experiencing some voltage transients on the TF bus, and the engineers want to keep the first few shots to a toroidal field of <= 5.6 T. |
| Aug 2 2012 09:20:21:903AM | 1120802001 | Geoff Olynyk | Starting step 1 of SL_PLAN. We repeat shot 1120622012 except with B-jet only firing, at t=1.000 s. RF heated at 1.0 MW to increase stored energy.
Result: No-power shot due to computer problems (IGOR failure in INIT). Shouldn't have brought donuts. Shot 1 basically vanished from the data system (tree didn't copy). B-port gas jet did fire successfully. Pressure after shot: Thermocouple gauge - 253.8 mtorr B-bottom MKS gauge - Don't seem to have any data from shot 1 Next shot - repeat of shot 1 (but with power). Despite this shot not existing in MDSplus, we're going to make the next one #002. |
| Aug 2 2012 09:36:27:727AM | 1120802002 | Geoff Olynyk | Shot 2:
Attempt baseline again. Target 1120622012 except with B-jet only firing, at t=1.000 s. RF heated at 1.0 MW to increase stored energy. Result: Another no-power shot due to data system problems. We skipped going into PULSE this time though, so the gas jet didn't fire. So we can take the next shot more quickly this time. Pressure after shot: Thermocouple gauge - N/A (didn't fire gas jet) B-bottom MKS gauge - N/A (didn't fire gas jet) Next shot: Data system test. Do not fire gas jets. |
| Aug 2 2012 09:44:48:857AM | 1120802003 | Geoff Olynyk | Shot 3
Plan: Data system test. Doing this test because then we can turn around the shot cycle quickly rather than firing the gas jet and waiting 20 minutes for pumpdown. Result: Data system worked. Next shot: Back to SL_PLAN, step 1. |
| Aug 2 2012 10:04:21:850AM | 1120802004 | Geoff Olynyk | Shot 4:
Attempt baseline again. Target 1120622012 except with B-jet only firing, at t=1.000 s. RF heated at 1.0 MW to increase stored energy. Result: Plasma. Gas jet didn't fire. B-jet was successfully enabled in MDSplus as we had a TTL pulse (look at /home/golynyk/scopes/gas_jets.dat). Nothing out of the interlock box though. Pressure after shot: Thermocouple gauge - no gas jet B-bottom MKS gauge - no gas jet Next shot: Repeat but (hopefully) fire gas jet. If it fails again, we'll bypass the interlock box. |
| Aug 2 2012 10:24:43:453AM | 1120802005 | Geoff Olynyk | Shot 5
Plan: Attempt baseline again. Target 1120622012 except with B-jet only firing, at t=1.000 s. RF heated at 1.0 MW to increase stored energy. Result: Successfully disrupted with gas jet. Good DMBolo toroidal asymmetry data. For some reason entered H-mode at 0.885 s. This is about the 20th time we've run this discharge and that has never happened before. Stored energy 100 kJ at time of mitigated disruption. Pressure after shot: Thermocouple gauge - 251.1 mtorr B-bottom MKS gauge - 362.5 mtorr Next shot: Move to step 2 of SL_PLAN (kappa=1.3 inner-wall limited discharge). |
| Aug 2 2012 10:33:42:487AM | 1120802006 | Geoff Olynyk | Shot 6
Plan: Moving to step 2 of SL_PLAN. Attempting low-elongation inner-wall limited plasma with kappa=1.3, Bt=5.18 T, Ip=750 kA, nl04 = 0.78. No RF. Result: Plasma ran beautifully. Gas jet fired successfully. Good DMBolo data. Pressure after shot: Thermocouple gauge - 245.7 mtorr B-bottom MKS gauge - 362.2 mtorr Next shot: Move to step 3 of SL_PLAN. Attempt for kappa=1.50 inner-wall limited plasma. |
| Aug 2 2012 10:58:45:167AM | 1120802007 | Geoff Olynyk | Shot 7
Plan: Moving to step 3 of SL_PLAN. Attempting low-elongation inner-wall limited plasma with kappa=1.5, Bt=4.28 T, Ip=750 kA, nl04 = 0.95. No RF. Result: Good plasma, good gas jet, good DMBolo. Pressure after shot: Thermocouple gauge - 245.7 mtorr B-bottom MKS gauge - 362.2 mtorr Next shot: We're goign to go to the high-elongation, low-field part of the scan because of ongoing TF power supply voltage transients. |
| Aug 2 2012 11:10:28:367AM | 1120802008 | Geoff Olynyk | Shot 8
Plan: Going to high-elongation (kappa ~ 1.58) inner-wall limited. kappa=1.58, Bt=3.98 T, Ip=750 kA, nl04 = 0.94. No RF. Result: Good plasma, good disruption. Pressure after shot: Thermocouple gauge - 235.4 mtorr B-bottom MKS gauge - 342.9 mtorr Next shot: Continuing elongation scan. Going to kappa=1.1, Bt=6.30 T, if we have permission from the engineers |
| Aug 2 2012 11:34:46:997AM | 1120802009 | Geoff Olynyk | Shot 9
Plan: Going to low-elongation (kappa ~ 1.1) inner-wall limited. kappa=1.10, Bt=6.30 T, Ip=750 kA, nl04 = 0.66. No RF. Result: Good disruption. Pressure after shot: Thermocouple gauge - 259.3 mtorr B-bottom MKS gauge - 380.5 mtorr Next shot: Going to very low elongation (kappa=1.01), Bt=6.9 T. |
| Aug 2 2012 11:46:08:113AM | 1120802010 | Geoff Olynyk | Shot 10
Plan: Going to lowest-elongation (kappa ~ 1.01) inner-wall limited shape for this scan. kappa=1.01, Bt=6.90 T, Ip=750 kA, nl04 = 0.63. No RF. Result: Good mitigated disruption. Pressure after shot: Thermocouple gauge - 248.4 mtorr B-bottom MKS gauge - 361.8 mtorr Next shot: Move to step 4 of SL_PLAN. Safety factor scan in elongated, LSN configuration. |
| Aug 2 2012 12:06:38:020PM | 1120802011 | Geoff Olynyk | Shot 11
Plan: Move to step 4 of SL_PLAN. Move to elongated, diverted (lower single-null) plasma and start safety factor scan at lowest q (lowest field). Want Bt=4.0 T, Ip=750 kA. Same shape and density as baseline (shot 005 from today). Result: Success. Pressure after shot: Thermocouple gauge - 227.2 mtorr B-bottom MKS gauge - 332.1 mtorr Next shot: Increase field to 5.0 T. |
| Aug 2 2012 12:20:57:973PM | 1120802012 | Geoff Olynyk | Shot 12
Plan: Increase field to 5.0 T (and thus safety factor). Plasma current remains at 750 kA. Density was a little low on the past one so PhysOp is increasing nl04 request. Result: Good disruption. Good density control. Pressure after shot: Thermocouple gauge - 240.3 mtorr B-bottom MKS gauge - 351.5 mtorr Next shot: Up field to 6.0 T. |
| Aug 2 2012 12:34:09:450PM | 1120802013 | Geoff Olynyk | Shot 13
Plan: Increase field to 6.0 T (and thus safety factor). Plasma current remains at 750 kA. Density request (nl04) as per last shot. Result: Good. Density target was dead-on. Pressure after shot: Thermocouple gauge - 240.3 mtorr B-bottom MKS gauge - 351.1 mtorr Next shot: Increase field to 7.0 T. |
| Aug 2 2012 12:46:38:223PM | 1120802014 | Geoff Olynyk | Shot 14
Plan: Increase field to 7.0 T. This is our highest field and safety factor for this scan. Plasma current remains at 750 kA. Density request (nl04) as per last shot. Result: Torus pressure after shot: Thermocouple gauge - 253.8 mtorr B-bottom MKS gauge - no data (reading –1400 mtorr) Next shot: Enter step 5 of SL_PLAN. Repeat elongation scan at constant safety factor in limited configuration. |
| Aug 2 2012 01:06:23:750PM | 1120802015 | Geoff Olynyk | Shot 15
Plan: Enter step 5 of SL_PLAN (repeat of elongation scan in limited configuration at constant safety factor). This shot is a repeat of shot 006 (kappa=1.30). Up the density slightly to get closer to target nebar of 1.55e20. Also change (delay) the timing of the Thomson pulses. Result: Good disruption. Density a little high (nebar ~ 1.68) Torus pressure after shot: Thermocouple gauge - 229.8 mtorr B-bottom MKS gauge - still messed up Next shot: Repeat shot 007. |
| Aug 2 2012 01:22:49:547PM | 1120802016 | Geoff Olynyk | Shot 16
Plan: Repeat of shot 007 (kappa=1.50). Lower the nl04 target by a couple percent to get closer to target nebar of 1.55e20. Also change (delay) the timing of the Thomson pulses. Result: Good. Dead on nebar target. Gas jet and DMBolo good. Torus pressure after shot: Thermocouple gauge - 237.7 mtorr B-bottom MKS gauge - 348.1 mtorr Next shot: Reload 009 (kappa=1.10). Up nl04 target a bit to get closer to nebar target of 1.55 |
| Aug 2 2012 01:35:58:933PM | 1120802017 | Geoff Olynyk | Shot 17
Plan: Repeat of shot 009 (kappa=1.10). Increase the nl04 target by a few percent to get closer to target nebar of 1.55e20. Also change (delay) the timing of the Thomson pulses. Result: Good. Torus pressure after shot: Thermocouple gauge - 229.8 mtorr B-bottom MKS gauge - 336.3 mtorr Next shot: Repeat shot 010 |
| Aug 2 2012 01:55:42:427PM | 1120802018 | Geoff Olynyk | Shot 18
Plan: Repeat of shot 010 (kappa=1.01). Increase the nl04 target by a ~7% to get closer to target nebar of 1.55e20. Also change (delay) the timing of the Thomson pulses. Result: Good disruption. Gas jet and DMBolo worked well. Density was a little low (nebar ~ 1.50). Torus pressure after shot: Thermocouple gauge - 232.4 mtorr B-bottom MKS gauge - 338.9 mtorr Next shot: Repeat of shot 008 (kappa=1.58) |
| Aug 2 2012 02:06:25:367PM | 1120802019 | Geoff Olynyk | Shot 19
Plan: Repeat of shot 008 (kappa=1.58). Also change (delay) the timing of the Thomson pulses. Result: Good. Density right on. Torus pressure after shot: Thermocouple gauge - 245.7 mtorr B-bottom MKS gauge - 358.8 mtorr Next shot: Move to step 6 of SL_PLAN. |
| Aug 2 2012 02:22:22:413PM | 1120802020 | Geoff Olynyk | Shot 20
Plan: Enter step 6 of SL_PLAN. Repeat of shot 011 (elongated LSN at Btor=4.0 T). Up the nl04 target relative to shot 011 to get closer to nebar target of 1.55. Delay second TS pulse vs. shot 011. Result: Very good. Density slightly low (nebar ~ 1.50). Big asymmetries. Four separate flashes of light on DMBolo! These diverted plasmas have MUCH more complicated disruption sequences. Torus pressure after shot: Thermocouple gauge - 235.3 mtorr B-bottom MKS gauge - 344.8 mtorr Next shot: Up field to 5.0 T (repeat of shot 012) |
| Aug 2 2012 02:35:23:190PM | 1120802021 | Geoff Olynyk | Shot 21
Plan: Repeat of shot 012 (elongated LSN at Btor=5.0 T). Delay Thomson pulses by 0.15 ms vs. shot 012. Result: Everything good. Density dead on. Torus pressure after shot: Thermocouple gauge - 248.2 mtorr B-bottom MKS gauge - Beserk again (no reading) Next shot: Up field to 6.0 T. |
| Aug 2 2012 02:44:21:460PM | 1120802022 | Geoff Olynyk | Shot 22
Plan: Repeat of shot 013 (elongated LSN at Btor=6.0 T). Leave nl04 target as is (was perfect on 013). Delay Thomson pulses by 0.15 ms vs. shot 013. Result: Fizzle. Gas jet still fired, though. Torus pressure after shot: Thermocouple gauge - 229.8 mtorr B-bottom MKS gauge - 336.7 mtorr Next shot: Repeat, without fizzle. |
| Aug 2 2012 03:04:14:080PM | 1120802023 | Geoff Olynyk | Shot 23
Plan: Repeat shot 22 but with plasma. Result: Good this time. Torus pressure after shot: Thermocouple gauge - 245.7 mtorr B-bottom MKS gauge - 359.8 mtorr Next shot: Repeat shot 014. Change nothing except Thomson timing. |
| Aug 2 2012 03:26:35:523PM | 1120802024 | Geoff Olynyk | Shot 24
Plan: Repeat of shot 014. Delay Thomson pulses by 0.15 ms. Density target same as 014. Result: Good disruption. Density (nebar) right on. Torus pressure after shot: Thermocouple gauge - 248.4 mtorr B-bottom MKS gauge - 356.8 mtorr Next shot: That's it for the written plan! Moving into bonus (unwritten) phase of SL_PLAN. We're going to redo shot 19 but with the elongation reduced slightly to 1.55. |
| Aug 2 2012 03:41:39:017PM | 1120802025 | Geoff Olynyk | Shot 25
Plan: Try high-elongation limited plasma again. Take shot 019 but reduce elongation slightly to prevent dithering between diverted and limited configurations. Aim for kappa=1.55 Result: Still flipping back and forth from limited to diverted. Good disruption though. Torus pressure after shot: Thermocouple gauge - 235.2 mtorr B-bottom MKS gauge - 341.9 mtorr Next shot: Reduce elongation a little more. And up field to 4.1 T. |
| Aug 2 2012 04:03:44:813PM | 1120802026 | Geoff Olynyk | Shot 26
Plan: Try again to get good limited discharge and high elongation. Aim for kappa=1.55 Result: Nice high-elongation limited plasma. Success. Torus pressure after shot: Thermocouple gauge - 227.2 mtorr B-bottom MKS gauge - 331.8 mtorr Next shot: Fire both gas jets into low-elongation limited plasma (plasma identical to shot 018). |
| Aug 2 2012 04:15:19:853PM | 1120802027 | Geoff Olynyk | Shot 27
Plan: We are going to repeat shot 18 exactly, except fire both gas jets in (with optimum timing). See Bob Granetz entry under MHD for timing information. Same Thomson timing as 018. Result: Good stuff. Both gas jets fired. Second Thomson pulse was too late (didn't see anything). Torus pressure after shot: Thermocouple gauge - 486.1 mtorr B-bottom MKS gauge - 716.0 mtorr Next shot: Repeat shot 015 and fire two gas jets. |
| Aug 2 2012 04:36:41:200PM | 1120802028 | Geoff Olynyk | Shot 28
Plan: We are going to repeat shot 15 exactly (inner-wall limited with kappa=1.30), except fire both gas jets in (with optimum timing). See Bob Granetz entry under MHD for timing information. Thomson timing to be advanced (earlier) on both pulses by 0.25 ms relative to shot 27. Result: F-jet didn't let a lot of gas through this time (only about 300 torr-l) but we'll take it. Both Thomson pulses got profiles. Torus pressure after shot: Thermocouple gauge - 314.2 mtorr B-bottom MKS gauge - 459.4 mtorr Next shot: Go to high elongation (repeat of shot 26). |
| Aug 2 2012 04:55:10:477PM | 1120802029 | Geoff Olynyk | Shot 29
Plan: We are going to repeat shot 026 exactly (inner-wall limited with kappa=1.57), except fire both gas jets in (with optimum timing). See Bob Granetz entry under MHD for timing information. Thomson timing to be identical to shot 028. Result: Good stuff. Again the F-jet didn't stay open very long (only about 3.1 ms), but we'll take it. That's it for our two-jet scan. Torus pressure after shot: Thermocouple gauge - 338.9 mtorr B-bottom MKS gauge - 497.6 mtorr Next shot: SUPER BONUS! Fire B-jet only into locked mode at t=0.850 s. |
| Aug 2 2012 05:12:50:010PM | 1120802030 | Geoff Olynyk | Shot 30
Plan: We are going to load a locked-mode discharge that creates a locked mode from t=0.800 s. We will fire the B-jet only at t=0.850 s. The reason for the earlier gas jet is because the locked modes often disrupt themselves before you get to t=1.000 s. Result: Successfully fired into locked mode. Torus pressure after shot: Thermocouple gauge - 229.8 mtorr B-bottom MKS gauge - 331.5 mtorr Next shot: That's it. Very successful run. Tons of stuff to look at. Thanks everyone! |
| Physics Operator Comments | |||
| Aug 2 2012 09:07:40:427AM | Bill Rowan | load shot 1120622012 segment 01 and 02 are on
import segment 1 from 1120731028 verify these: BT = 5.6 T, 154900 A IP = 1 MA changed engineering reference shot to 1120611012 set gatevalve toggle to on and set it for 60 s torus pressure before the run is 2.1e-07 T | |
| Aug 2 2012 09:25:22:577AM | 1120802001 | Bill Rowan | 001.
no power shot due to computer problems gate valve remained closed as requested 2.7e-07 before the next shot |
| Aug 2 2012 09:33:50:167AM | 1120802002 | Bill Rowan | 002.
no power shot as 001 |
| Aug 2 2012 09:34:31:393AM | 1120802002 | Bill Rowan | bypassed pulse and went to recool
|
| Aug 2 2012 09:35:25:540AM | 1120802002 | Bill Rowan |
gas injection will be off until we get a plasma shot |
| Aug 2 2012 09:42:34:287AM | 1120802003 | Bill Rowan | 003.
data system test no power shot |
| Aug 2 2012 09:56:32:770AM | 1120802004 | Bill Rowan | 004.
plasma no gas jet plasma full length into ramp down 1 MW ICRF as requested |
| Aug 2 2012 10:23:20:580AM | 1120802005 | Bill Rowan | 005.
plasma disruption at 1.0 s for next shot load from 1100908011 import segment 1 from 1120802005 recalculated predictors Rcur, zcur, rxl, zxl, rxu,zxu, pg1 (ar puff) set to 0.3 s and run for 60 ms enabled pg1 BT = 0.5.18T iP = 0.75MA nl_04 = 0.78e+20 |
| Aug 2 2012 10:42:14:343AM | 1120802006 | Bill Rowan | 006.
plasma disruption at 1 s 0.752 MA 0.82e+20 5.2T kappa = 1.3 next shot Bt = 4.28T, 117904 nl_04 = 0.95e+20 clearin = -0.025 for a kappa of 1.5 |
| Aug 2 2012 10:53:38:537AM | 1120802007 | Bill Rowan | 007.
plasma disruption at 1 s 4.35 T kappa = 1.5 nl_04 = 1.0e+20 |
| Aug 2 2012 10:59:01:427AM | 1120802007 | Bill Rowan | 007.
plasma disruption at 1 s 4.35 T kappa = 1.5 nl_04 = 1.0e+20 next shot. BT = 3.98T, 109639 nl_04 = 0.97e+20 clearin = -0.017 for a kappa of 1.58 |
| Aug 2 2012 11:19:07:583AM | 1120802008 | Bill Rowan | 008.
plasma BT = 4.06T nl_04 = 1/02e+20 kappa - 1.64 next shot Bt = 6.3 T, 173550 nl_04 = 0.68e+20 clearin = -0.075 for kappa =1.1 |
| Aug 2 2012 11:37:04:760AM | 1120802009 | Bill Rowan | 009.
BT = 6.24 T nl_04 = 0.70e+20 kappa = 1.14 next shot. BT = 6.9T, 190078 nl_04 =0.63e+20 clearin = -0.1 |
| Aug 2 2012 11:53:01:703AM | 1120802010 | Bill Rowan | 010.
BT = 6.8T iP = 756 kA kappa = 1.0 nl_04 = 0.65e+20 next shot reload 1120802005 BT = 4.0T, 110190 ip = 0.75 MA |
| Aug 2 2012 12:09:12:263PM | 1120802011 | Bill Rowan | 011.
plasma IP = 0.74MA BT = 4.1T nl+04 = 0.84e_20 kappa = 1.57 next shot increase nl_04=1.1e+20 BT=5 T, 137740 |
| Aug 2 2012 12:19:29:053PM | 1120802012 | Bill Rowan | 012.
plasma BT = 5.0T nl_04 = 0.92e+20 IP = 0.75 MA next shot. BT = 6 T, 165285 |
| Aug 2 2012 12:32:30:830PM | 1120802013 | Bill Rowan | 013.
plasma BT=6.0T next shot. BT = 7.0T, 192833 |
| Aug 2 2012 12:51:17:590PM | 1120802014 | Bill Rowan | 014.
plasma BT = 6.9 T next shot reload 1120802006 nl_04 = 0.83e+20 |
| Aug 2 2012 01:04:02:773PM | 1120802015 | Bill Rowan | 015.
plasma next shot reload 1120802007 nl_04 = 0.93e+20 |
| Aug 2 2012 01:17:15:663PM | 1120802016 | Bill Rowan | 016.
plasma next shot reload 1120802009 |
| Aug 2 2012 01:34:33:640PM | 1120802017 | Bill Rowan | 017.
plasma next shot. reload 1120802010 |
| Aug 2 2012 01:48:59:557PM | 1120802018 | Bill Rowan | 018.
plasma next shot. reload 1120802008 |
| Aug 2 2012 02:05:05:397PM | 1120802019 | Bill Rowan | 019.
plasma next shot reload 1120802011 |
| Aug 2 2012 02:26:09:320PM | 1120802020 | Bill Rowan | 020.
plasma next shot reload 110802012 |
| Aug 2 2012 02:34:01:347PM | 1120802021 | Bill Rowan | 021.
plasma next shot reload 1120802013 |
| Aug 2 2012 02:54:13:350PM | 1120802022 | Bill Rowan | 022.
fizzle next shot. no pcs changes |
| Aug 2 2012 03:02:04:930PM | 1120802023 | Bill Rowan | 023.
plasma next shot. reload 1120802014 |
| Aug 2 2012 03:26:53:583PM | 1120802024 | Bill Rowan | 024.
plasma next shot reload 1120802019 reduce elongation slightly clearin from -0.017 to -0.018 |
| Aug 2 2012 04:04:05:943PM | 1120802025 | Bill Rowan | 025.
plasma next shot. reduce elongation slightly clearin from -0.018 to -0.20 increase TF from 4.0 T to 4.1 T, 112945 |
| Aug 2 2012 04:03:41:200PM | 1120802026 | Bill Rowan | 026.
plasma kappa = 1.58 next shot reload 1120802018 2 gas jets on this shot |
| Aug 2 2012 04:34:11:670PM | 1120802028 | Bill Rowan | 028.
plasma next shot reload 1120802026 |
| Aug 2 2012 04:54:59:460PM | 1120802029 | Bill Rowan | 029
plasma next shot reload 1120725004, turn off segment 02, turn on segment 04 import segment 1 from 1120802029 |
| Aug 2 2012 05:14:33:183PM | 1120802030 | Bill Rowan | 030.
plasma locked at 0.62 or a little later -- frcece or soft x-rays last shot. |
| Engineering Operator Comments | ||||
| Shot | Time | Type | Status | Comment |
| 1 | 09:10:00:937AM | Test | Bad | |
| 2 | 09:28:32:397AM | Test | Bad | |
| 3 | 09:40:33:463AM | Test | Ok | data cycle |
| 4 | 09:48:35:687AM | Plasma | Ok | |
| 5 | 10:05:55:387AM | Plasma | Ok | |
| 6 | 10:27:38:327AM | Plasma | Ok | |
| 7 | 10:49:29:830AM | Plasma | Ok | |
| 8 | 11:05:49:230AM | Plasma | Ok | |
| 9 | 11:26:22:243AM | Plasma | Ok | |
| 10 | 11:42:39:067AM | Plasma | Ok | |
| 11 | 11:58:29:940AM | Plasma | Ok | |
| 12 | 12:13:14:903PM | Plasma | Ok | |
| 13 | 12:26:11:720PM | Plasma | Ok | |
| 14 | 12:40:37:080PM | Plasma | Ok | |
| 15 | 12:57:14:450PM | Plasma | Ok | |
| 16 | 01:14:48:100PM | Plasma | Ok | |
| 17 | 01:30:38:953PM | Plasma | Ok | |
| 18 | 01:44:41:153PM | Plasma | Ok | |
| 19 | 01:58:10:503PM | Plasma | Ok | |
| 20 | 02:12:38:480PM | Plasma | Ok | |
| 21 | 02:26:08:883PM | Plasma | Ok | |
| 22 | 02:39:46:980PM | Plasma | Ok | |
| 23 | 02:57:33:633PM | Plasma | Ok | |
| 24 | 03:17:01:420PM | Plasma | Ok | |
| 25 | 03:35:58:710PM | Plasma | Ok | |
| 26 | 03:53:55:980PM | Plasma | Ok | |
| 27 | 04:10:50:443PM | Plasma | Ok | |
| 28 | 04:30:48:907PM | Plasma | Ok | |
| 29 | 04:48:57:047PM | Plasma | Ok | |
| 30 | 05:06:34:677PM | Plasma | Ok | |
| System Availability | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Aug 2 2012 09:08:22:307AM | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Aug 2 2012 03:53:32:813PM | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Brightness calibration for PMTs (LFS viewing)
use UV labsphere, connect fiber #58 (0.4mm) to PMT; 720 Background (UV off) 721 repeat 722 repeat PMT CH1: 723 voltage: 0.5 diode: 0.546e-6 A 724 voltage: 0.6 diode: 0.546e-6 A 725 voltage: 0.7 diode: 0.540e-6 A 726 voltage: 0.8 diode: 0.540e-6 A 727 voltage: 0.9 diode: 0.539e-6 A 728 voltage: 1.0 diode: 0.539e-6 A 729 voltage: 1.01 diode: 0.546e-6 A taken at later time Does not work: voltages 1.09, 1.05,1.02 Works: 1.01 Works: 0.48,0.46 Does not work: 0.45 PMT CH2: 730 background (ch 2 on 0.5) 731 voltage: 0.5 diode: 0.547e-6 A 732 voltage: 0.6 diode: 0.546e-6 A 733 voltage: 0.7 diode: 0.546e-6 A 734 voltage: 0.8 diode: 0.547e-6 A 735 voltage: 0.9 diode: 0.548e-6 A 736 voltage: 1.0 diode: 0.549e-6 A 737 voltage: 1.01 diode: 0.546e-6 A does not work does not work: 1.1, PMT CH3: 738 background (Ch 3 on 0.5) 739 voltage: 0.5 diode: 0.546e-6 A 740 voltage: 0.6 diode: 0.546e-6 A 741 voltage: 0.7 diode: 0.546e-6 A 742 voltage: 0.8 diode: 0.546e-6 A 743 voltage: 0.9 diode: 0.545e-6 A 744 voltage: 1.0 diode: 0.546e-6 A 745 voltage: 1.03 diode: 0.545e-6 A does not work PMT CH4: 746 background (Ch 4 on 0.5) 747 voltage: 0.5 diode: 0.547e-6 A 748 voltage: 0.6 diode: 0.547e-6 A 749 voltage: 0.7 diode: 0.547e-6 A 750 voltage: 0.8 diode: 0.549e-6 A 751 voltage: 0.9 diode: 0.546e-6 A ? 752 voltage: 1.0 diode: 0.423e-6 A (had to turn lamp down a bit...) 753 voltage: 1.03 diode: 0.424e-6 A does not work not sure about 752, repeat it later... 770 voltage: 1.0 diode: 0.386e-6 A PMT CH5: 754 background (Ch 5 on 0.5) 755 voltage: 0.5 diode: 0.386e-6 A 756 voltage: 0.6 diode: 0.387e-6 A 757 voltage: 0.7 diode: 0.385e-6 A 758 voltage: 0.8 diode: 0.386e-6 A 759 voltage: 0.9 diode: 0.386e-6 A 760 voltage: 1.0 diode: 0.386e-6 A 761 voltage: 1.03 diode: 0.386e-6 A does not work PMT CH6: need to turn lamp further down... 762 background (Ch 6 on 0.5) 763 voltage: 0.5 diode: 0.283e-6 A 764 voltage: 0.6 diode: 0.284e-6 A 765 voltage: 0.7 diode: 0.283e-6 A 766 voltage: 0.8 diode: 0.283e-6 A 767 voltage: 0.9 diode: 0.284e-6 A 768 voltage: 1.0 diode: 0.284e-6 A 769 voltage: 1.03 diode: 0.285e-6 A does not work Transmission of fiber #58: 771 #58 and #57 connected to Ch6 (voltage 0.8, diode: 0.286e-6 A) 772 #57 connected to Ch6 (voltage 0.8, diode: 0.283e-6 A) 773 background repeat 774 #58 and #57 connected to Ch6 (voltage 1.0, diode: 0.282e-6 A) 775 #57 connected to Ch6 (voltage 1.0, diode: 0.286e-6 A) 776 background | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Aug 2 2012 06:57:38:630PM | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Wavelength Calibrations
SETUP Fstop: 1.8/1.8 Controller Gain: 2/2 ADC Offset: 225/200 photonSetup.pro Number of Frames: 20 Length of Frames: 300 msec Time to Start: 0.00 sec Spectrometers WERE refocused before calibration 780 background 781 A1 A7 A13 782 A2 A8 A14 783 A3 A9 A15 784 A4 A10 A16 785 A5 A11 A17 786 A6 A12 A18 787 B1 B7 B13 788 B2 B8 B14 789 B3 B9 B15 790 B4 B10 B16 791 B5 B11 B17 792 B6 B12 B18 793 C1 C7 C13 794 C2 C8 C14 795 C3 C9 C15 796 C4 C10 C16 797 C5 C11 C17 798 C6 C12 C18 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||