| Miniproposals | ||||||||||
|
| Operators | |
| Session leader(s): | Yuichi Takase |
| Physics operator(s): | John Goetz |
| Engineering operator(s): | Unknown |
| Engineering Operator Run Comment |
| TF Power supply test. |
| Session Leader Plans |
| Physics Operators Plans |
| Session Leader Summaries |
| Physics Operator Summaries |
| Session Leader Comments | |||
| May 6 1993 08:44:36:150AM | Yuichi Takase | Today's run plan (May 6, 1993):
Try to fix the TF crowbar problem. If TF fixed, will continue where we left off yesterday and try for plasma. (An entry like this was made for Run 930505 Shot 930505009. Ignore it.) | |
| May 7 1993 08:16:40:350AM | John Goetz | test -- can Goetz write?
| |
| May 7 1993 08:44:03:690AM | John Goetz |
This case's waveforms come from USER10:[WOLFE.MDS.SHOTS.HYBRID.PCS]PCS_141.*; The simulated shot data is in CMOD_SIM$ROOT: shot #141. The scenario in PCS_141 has the following properties: Commutation resistors: OH1 0.156 Ohm OH2U&L 0.035 EF1U&L 0.236 OH1, OH2U&L, EF1U&L and EF4: ON= -1.60 sec CLOSE= -1.55 OPEN= 0. (OH1,OH2U&L,EF1U&L only) CROWBAR=0.030 (OH1,OH2U&L,EF1U&L only) INVERT= 0.250 EF3: ON= anytime before -.050 sec INVERT= +.250 EF2U&L each have ballast resistor = 35e-3 Ohm (not critical) ON= anytime before 0.0 sec CLOSE= 0.030 INVERT=0.250 PLC current limits at or above drawn waveforms, eg OH1 20kA OH2U&L 17kA EF1U&L 10kA EF2U&L 5kA EF3 12kA (supply current) EF4 4kA The plasma is assumed to breakdown at 0.020 sec, and rise at 1.e6 A/sec. | |
| May 6 1993 09:16:15:700AM | 930506001 | Yuichi Takase | All subtrees not needed for TF tests have been turned off this morning. They
will be turned back on when plasma tests are started. |
| May 6 1993 09:53:46:170AM | 930506001 | Yuichi Takase | TF2 15kA failing at inversion (single phasing)
|
| May 6 1993 10:09:24:030AM | 930506002 | Yuichi Takase | same, TF2 breaker (TF3 cabinet), same fault
|
| May 6 1993 10:10:33:180AM | 930506003 | Yuichi Takase | fixed, 15kA TF3 cabinet, OK
|
| May 6 1993 10:11:11:650AM | 930506004 | Yuichi Takase | 30kA TF3 cabinet, OK
|
| May 6 1993 10:16:10:400AM | 930506005 | Yuichi Takase | 15kA TF4 cabinet (TF2 breaker), commutation failure
|
| May 6 1993 10:34:01:130AM | 930506006 | Yuichi Takase | 15kA TF4 cabinet, OK
|
| May 6 1993 10:36:05:240AM | 930506007 | Yuichi Takase | 30kA TF4 cabinet, commutation failure during rampdown
|
| May 6 1993 11:01:59:740AM | 930506008 | Yuichi Takase | 15kA TF4 OK
Testing EF3 resistance measurement for noise, and also looking for voltage spikes. EF3 supply on and breaker closed with 0 programmed voltage. |
| May 6 1993 11:06:52:480AM | 930506009 | Yuichi Takase | 30kA TF4 OK
No change in EF3 bus voltage. Removed short (back to normal). |
| May 6 1993 11:18:49:130AM | 930506010 | Yuichi Takase | Previous two shots were TF7, not TF4.
TF8 15kA OK. |
| May 6 1993 11:26:50:870AM | 930506011 | Yuichi Takase | TF8 30kA OK.
|
| May 6 1993 11:48:25:910AM | 930506012 | Yuichi Takase | TF7 + TF8 60kA commutation failure. Faulted at 18kA.
|
| May 6 1993 11:57:26:420AM | 930506013 | Yuichi Takase | TF7 + TF8 25kA commutation failure (same).
|
| May 6 1993 12:06:10:510PM | 930506014 | Yuichi Takase | Previous entry was for shot 14.
TF7 + TF8 25kA OK. EF3 open. |
| May 6 1993 12:11:14:380PM | 930506015 | Yuichi Takase | TF7 + TF8 50kA commutation fault at 35kA
|
| May 6 1993 12:29:02:860PM | 930506016 | Yuichi Takase | TF7 + TF8 50kA commutation fault at 35kA (same)
|
| May 6 1993 01:12:11:500PM | 930506017 | Yuichi Takase | TF7 + TF8 50kA commutation fault at 35kA (same)
|
| May 6 1993 01:31:53:260PM | 930506018 | Yuichi Takase | TF7 + TF8 50kA commutation fault at 35kA (same)
|
| May 6 1993 01:47:17:410PM | 930506019 | Yuichi Takase | TF7 + TF8 50kA OK. (commutation fault disabled)
|
| May 6 1993 01:56:28:620PM | 930506020 | Yuichi Takase | No trigger
|
| May 6 1993 01:58:38:590PM | 930506021 | Yuichi Takase | TF7 + TF8 60kA regulated OK, inverted OK.
|
| May 6 1993 02:29:46:870PM | 930506022 | Yuichi Takase | TF7 + TF8 45kA OK.
|
| May 6 1993 02:48:08:220PM | 930506023 | Yuichi Takase | TF7 + TF8 45kA OK.
|
| May 6 1993 04:28:12:340PM | 930506024 | Yuichi Takase | TF7 + TF8 45kA OK.
|
| May 6 1993 04:28:37:180PM | 930506025 | Yuichi Takase | TF7 + TF8 45kA OK.
|
| May 6 1993 04:28:50:680PM | 930506026 | Yuichi Takase | TF7 + TF8 45kA OK.
|
| May 6 1993 04:29:02:920PM | 930506027 | Yuichi Takase | TF7 + TF8 45kA OK.
|
| May 6 1993 04:29:14:700PM | 930506028 | Yuichi Takase | TF7 + TF8 45kA OK.
|
| May 6 1993 04:29:26:720PM | 930506029 | Yuichi Takase | TF7 + TF8 45kA OK.
|
| May 6 1993 04:32:19:380PM | 930506030 | Yuichi Takase | TF7 + TF8 60kA OK. Problem fixed.
|
| May 6 1993 05:05:22:200PM | 930506031 | Yuichi Takase | TF4 15kA OK.
|
| May 6 1993 05:05:38:220PM | 930506032 | Yuichi Takase | TF4 30kA OK.
|
| May 6 1993 05:06:20:390PM | 930506033 | Yuichi Takase | TF3 + TF4 50kA OK.
|
| May 6 1993 05:13:11:920PM | 930506034 | Yuichi Takase | TF3+4+7+8 100kA OK.
|
| May 6 1993 05:28:09:930PM | 930506035 | Yuichi Takase | TF3+4+7+8 105kA IOC (instantaneous overcurrent) fault on 4.
Pressure is reading 4E-7. End of run. |
| Physics Operator Comments |
| Engineering Operator Comments | ||||
| Shot | Time | Type | Status | Comment |
| 1 | 09:12:43:870AM | Test | Ok | test shot good 15 k Amp Bypass didn't operate with emergrcy off button. |
| 2 | 09:41:30:110AM | Test | Bad | need to disable gate extender bd. |
| 3 | 09:56:23:070AM | Test | Ok | good shot. |
| 4 | 10:04:11:430AM | Test | Ok | Good Shot |
| 5 | 10:11:27:200AM | Test | Bad | Bad comm. con. bd. |
| 6 | 10:23:39:580AM | Test | Ok | Good shot Com,conduction bd. disconnected. |
| 7 | 10:28:51:780AM | Test | Bad | comutation fail in inversion |
| 8 | 10:54:56:810AM | Test | Ok | Good shot cabinet # 7 15 k amp |
| 9 | 11:03:03:390AM | Test | Ok | Good shot 30 Kamp |
| 10 | 11:14:37:890AM | Test | Ok | Good pulse Cabinet 8 15kamp. |
| 11 | 11:19:48:130AM | Test | Ok | Good shot 30 Kamps cabinet # 8. |
| 12 | 11:34:29:900AM | Test | Bad | asking for 60 Kamps commutation failure at 18 kamp cabinet #4 |
| 13 | 11:49:21:220AM | Test | Bad | Cabinet #4 fault |
| 14 | 12:00:12:920PM | Test | Ok | good |
| 15 | 12:05:54:090PM | Test | Ok | cabint #4 Faulted at 35 kamp asking for 50 KA. |
| 16 | 12:21:47:450PM | Test | Bad | TF Crowbar exact same place |
| 17 | 12:48:07:270PM | Test | Bad | TF Crowbar same |
| 18 | 01:08:07:340PM | Test | Bad | same problem |
| 19 | 01:38:23:240PM | Test | Ok | 50KA pulse cabinet #4 no fault . |
| 20 | 01:48:19:520PM | Test | Bad | No Camac |
| 21 | 01:52:27:660PM | Test | Ok | good 60 kA test with comm fault disconnected in TF |
| 22 | 02:25:10:060PM | Test | Ok | 45 kA TF 4 with comm fail disconnected |
| 23 | 02:42:19:660PM | Test | Ok | 45 Kamp shot Converter #4. |
| 24 | 02:54:58:650PM | Test | Ok | Good Shot cheaking Master commutation, conduction bd. for faults |
| 25 | 03:06:29:490PM | Test | Ok | Good Testing comm. cond. master Bd. |
| 26 | 03:18:42:770PM | Test | Ok | Test Pulse O.K. |
| 27 | 03:27:05:580PM | Test | Ok | Testing com. cond. Bd. |
| 28 | 03:38:18:260PM | Test | Ok | Commutation conductance board test |
| 29 | 04:12:28:650PM | Test | Ok | commutation bd test |
| 30 | 04:18:47:530PM | Test | Ok | good |
| 31 | 04:49:08:960PM | Test | Ok | good |
| 32 | 04:54:36:390PM | Test | Ok | good |
| 33 | 05:02:13:210PM | Test | Ok | 50 kamp pulse converter #2 good |
| 34 | 05:08:52:800PM | Test | Ok | 100 KA shot good |
| 35 | 05:18:51:980PM | Test | Bad | faulted in inverson |